Klaxalarm Boxer (17-970303)
Battery Operated - Manual Call Point/Sounder
The Manual Call Point has a built-in alarm sounder and is powered by batteries. Up to 12 units can be connected
together using 2 core screened fire proof cable (the screen core is used as a negative). The indicating LED will
light on operation of the device(s) and switch off on resetting.
The Batteries should be replaced once every 12 months. The unit does not draw any current from the batteries until
operated. There is no low battery warning feature but as the battery voltage falls a slight drop in sound output is
noticeable during normal testing.
1. Installation
Surface Mounting
Fix the surface back box to a flat vertical surface using at least two of the
four mounting holes provided.
The back box may be drilled to allow cable access, a step drill is the most
efficient and least stressful to the moulding. A 20mm hole is provided in
the rear.
NOTE Please ensure that the spade connectors are located exactly as
per diagram (shown right) else the battery may foul against them
Terminations/Connections
When interlinking more than one unit - cabling may be connected into the
terminals provided (Red=Permanent positive, Blue=Common Negative,
Yellow=Switched Positive). Although there are three conductors a 2 core
screen cable can be used, as the screen may be utilised.
If using Pirelli FP200 then wire as Red:RED, Black:YELLOW,
Screen:BLUE.
Flush Mounting
The Call Point may be flush mounted utilising the optional flush bezel, combined
with any standard single gang flush mounting back box (with a minimum internal
depth of 25mm). After installing the back box securely, attach the bezel using the
two M3 screws
Call Point 1st fix testing
Please remember that all high voltage testing must be carried out before the installation of the Call Point front unit
as this may cause damage.
Klaxon Signals Ltd
Wrigley St
Oldham
England
OL4 1HW
Technical Helpline:
Sales Hotline:
Fax:
E-mail:
Web:
+44 (0) 161 287 4029
+44 (0) 161 287 5555
+44 (0) 161 287 5511
|