POWER AVAILABILITY
USER MANUAL
PowerSure™ PST
500-650 VA
230V
Transient Voltage Surge Suppression (TVSS) & EMI / RFI
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Transfer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Inverter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fault Indicator (Red) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Location and Status of Indicators . . . . . . . . . . . . . . . . . . . . . . . . . 11
Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
USB Interface Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Cleaning the UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Maintaining Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Guide to Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Troubleshooting Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Battery Run Times. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
i
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be fol-
lowed during the installation and maintenance of the Uninterruptible
Power System (UPS) and its batteries. Please read this manual thor-
oughly before attempting to install or operate this UPS.
Read all safety, installation, and operating instructions before operat-
ing the UPS. Adhere to all warnings on the unit and in this manual.
Follow all operating and user instructions.
This equipment is designed for Commercial, Industrial or Home use.
Liebert Corporation neither recommends nor knowingly sells this
product for use in life support applications or with other designated
critical devices.
This equipment can be installed and operated by individuals without
previous training.
WARNING
!
SAFETY PRECAUTIONS
• There are no user-serviceable parts inside this UPS. Refer
all UPS and battery service to qualified service personnel.
Do not attempt to service this product yourself.
• Output receptacles on the UPS are electrically live if the
UPS is switched on, even if the UPS is not plugged into a
Mains supply. The ON/OFF button on the UPS does not elec-
trically isolate the internal parts. Some components are live
even when Mains power is disconnected. To isolate the UPS,
switch off the UPS first, then unplug it from the Mains.
• Opening or removing the cover may expose you to lethal
voltages within this unit even when it is apparently not
operating and the input wiring is disconnected from the
electrical source.
• Observe all CAUTION and WARNING statements in this
manual and on the unit. Failure to do so may result in
serious injury or death.
• Never work alone.
• This UPS should not be supplied from electrical power sys-
tems of the “IT” (Impedance á Terre) type (IEC 364 - Elec-
trical Installation of Buildings).
• The UPS must be earthed/grounded at all times during
operation. Connect only to a mains supply socket outlet
with an earth/ground connection.
1
CAUTION
!
Although your UPS has been designed and manufactured to
assure personal safety, improper use may result in electrical
shock or fire. To ensure safety, please observe the following
rules:
• Turn off and unplug your UPS before cleaning. Do not use
liquid or aerosol cleaners. A dry cloth is recommended to
remove dust from the surface of your UPS.
• Do not install or operate your UPS in or near water.
• Do not place your UPS on an unstable cart, stand or table.
• Do not place your UPS in direct sunlight or near heat
emitting sources.
• Never block or insert any objects into the ventilation holes
or other openings of the UPS. Keep all vents free of dust
accumulation that could restrict airflow.
• Do not place UPS power cord in any area where it may be
damaged by heavy objects.
• Placing magnetic storage on the top of the UPS may result
in data corruption.
CAUTION
!
BATTERY HANDLING PRECAUTIONS
Servicing of batteries should be performed or supervised by
personnel knowledgeable of batteries and required
precautions. Keep unauthorized personnel away from the
batteries.
A battery can present a risk of electrical shock and high
short-circuit current. The following precautions should be
observed when working on batteries:
• Remove watches, rings, and other metal objects.
• Use tools with insulated handles.
• Do not dispose battery or batteries in a fire. The battery
may explode.
• Do not open or mutilate the battery or batteries. Released
electrolyte is harmful to skin and eyes. It may be toxic.
• When replacing the battery, use same number and type of
battery as the suitable recommended type of battery listed
in specification table in back of this manual.
• Handle, transport and recycle batteries in accordance with
local regulations.
2
CAUTION
!
If your UPS demonstrates any of the following conditions,
turn off and unplug your UPS from the outlet and contact
your local dealer, Liebert representative, or Liebert
Worldwide Support Group.
• The power cord is damaged.
• Liquid has been spilled on the UPS.
• The circuit breaker or fuse opens frequently.
• The UPS does not operate in accordance with the user
manual.
Electromagnetic Compatibility—The PowerSure™ PST series
complies with the requirements of the EMC Directive 89/336/EEC and
the published technical standards. Continued compliance requires
installation in accordance with these instructions and use of Liebert
approved accessories only.
Environmental—Operate the UPS in an indoor environment only in
an ambient temperature range of 0°C to 40°C (32°F to 104°F). Install
in a clean environment, free from conductive contaminates, moisture,
flammable liquids, gases, or corrosive substances.
Provided is a USB cable for connection to a computer. Store in a safe
place if not required at this time.
3
INTRODUCTION AND SYSTEM DESCRIPTION
Congratulations on your choice of the Liebert PowerSure™ PST Unin-
terruptible Power System (UPS). It provides filtered AC power to sen-
sitive electronic equipment and other critical loads.
The PowerSure PST is an off-line UPS designed for desktop applica-
tions. It provides perfect one-to-one power protection for electronic
equipment such as PCs, point-of-sale displays, home office equipment
and similar electronic gear. The PowerSure PST is available in two (2)
sizes: 500 and 650VA at 230VAC.
PowerSure PST models are available for 120VAC and 230VAC supply
voltages and loads. Please verify that this model matches your AC
Mains and load voltage requirements.
4
Top and Side Views of UPS
Black output receptacles
Surge protection only
AC Inlet
TOP OF UPS
Mains/Battery Indicator
(Green)
Fault Indicator (Red)
Orange output receptacles
Battery backup + surge protection
RIGHT SIDE OF UPS
USB interface
port (for
PAXXX-230U
models only)
LEFT SIDE OF UPS
Data Line
Protection
Connectors
(IN, OUT, OUT)
Phone/Fax/DSL/
Internet/Modem
Devices
Refer to Bottom for
Cautionary Markings
Circuit Protector
5
MAJOR COMPONENTS
Input
Output
L
TVSS &
EMI/RFI
Filters
Transfer
Switch
L
Battery
Charger
Battery
Inverter
N
G
N
G
Transient Voltage Surge Suppression (TVSS) & EMI / RFI
Filters
These UPS components provide surge protection and filter electro-
magnetic interference (EMI) and radio frequency interference (RFI).
They minimize surges or interference present in the mains line and
keep the sensitive equipment protected.
Transfer Switch
In Normal mode the Transfer Switch passes mains AC power to the
connected load. When input mains voltage or frequency is outside
acceptable limits, the transfer switch activates and transfers the UPS
to battery.
Battery Charger
In Normal mode, the Battery Charger converts mains AC power into
regulated DC power to float charge the battery. It is continuously
charging the battery whenever the UPS is plugged into a power outlet
and mains power is within acceptable limits—even if the UPS is
turned OFF.
Battery
The PowerSure PST utilizes a valve-regulated, nonspillable, lead acid
battery. To optimize battery life, operate the UPS in an ambient tem-
perature of 20°-25°C (68°-77°F).
Inverter
When mains power fails, the Inverter draws energy from the battery
and inverts it into a regulated stepped sinewave supplying power for
equipment connected to the orange receptacles.
6
WHAT’S INCLUDED
The PowerSure PST is shipped with the following items:
• PowerSure PST user manual
• USB cable (PAXXX-230U models only), 1.8m (6 ft.)
• RJ-11 cord, 2.1m (7 ft.)
• Two (2) 10A output power cords, 2.0m (6.6 ft.)
USB cable
PowerSure PST
1.8m (6 ft.)
(for PAXXX-230U
models only)
Two (2) 10A
RJ-11 cord
output power cords
2.1m (7 ft.)
2.0m (6.6 ft.)
7
INSTALLATION
This UPS is designed for data processing equipment. Maximum load
must not exceed that shown on the UPS rating label. Do not connect
equipment that could overload the UPS or draw half-wave current
from the UPS, for example: electric drills, vacuum cleaners, laser
printers or hair dryers. Your total load earth leakage current must not
exceed 3.5 mA. Most data processing equipment meets this require-
ment if you use no more than two pieces of equipment. If uncertain
about your load, consult your local dealer, Liebert representative, or
Liebert Worldwide Support Group.
1. Visually inspect the UPS for freight damage. Report damage to the
carrier and your local dealer, Liebert representative or the Liebert
Worldwide Support Group.
2. Decide where to place the PowerSure PST. Install the UPS indoors
in a controlled environment, where it cannot be accidentally turned
off. Place it in an area of unrestricted airflow around the unit, away
from water, flammable liquids, gases, corrosives, and conductive
contaminants. Maintain an ambient temperature range of 0°C to
40°C (32°F to 104°F).
NOTE
UPS operation in temperatures above 25°C (77°F) reduces
battery life.
Plug this type of equipment into black
receptacles ONLY.
Inkjet
Printer
Scanner
FAX
Machine
Plug computers, monitors & network hubs
into orange receptacles.
3. The PowerSure™ PST 230VAC models are not supplied with an
input power lead for connection to the mains supply. Additional
input/output leads can be obtained from your dealer.
8
4. Shut down the load equipment and turn off the mains supply.
Unplug the load equipment’s power input cable from the mains sup-
ply socket and plug it into the UPS input socket. Plug the power
input cable into the mains supply socket.
Connect the supplied output cable between the load equipment
input socket and one of the UPS AC output sockets. Connect all load
equipment to the UPS in this manner.
5. Plug any computers and monitors into the orange battery backed up
receptacles.
Other office machines that do not exceed the capacity of the UPS—
inkjet printers, scanners and fax machines—may be plugged into
either of the two (2) black receptacles, which provide surge protec-
tion only.
6. Connect Phone/Fax/DSL/Internet/Modem devices to data line con-
nectors.
om for
arkings
7. Press and release the ON/OFF/Alarm Silence button to turn on the
UPS. The UPS will beep and the Mains/Battery Indicator will illu-
minate (green).
8. Turn on connected equipment.
9. If your PST has the optional USB port (available on models with
extension “-230U”):
Connect the USB cable provided with the UPS to the USB ports on
the PST and your computer. The PST will work automatically with
your built-in power management software on Windows XP and 2000
and Mac OS 10.2 or later (see USB Interface Port section for
details).
NOTE
When using the communication features on this UPS, ensure
the cabling connected to the UPS communications ports are
kept separated from the power leads to the UPS input and
output.
9
CONTROLS AND INDICATORS
ON/OFF/Alarm Silence Button
This button controls output power to the
connected load and has three functions:
• ON
• OFF
• Alarm Silence
ON/OFF/Alarm Silence
ON
When the UPS is off, pressing the main ON/OFF button for
more than two seconds will start the UPS, and an audible
alarm sounds briefly. The UPS is capable of starting on bat-
tery (battery start).
OFF
When the UPS is on (in either Normal or Battery mode),
pressing the main ON/OFF button for more than
two (2) seconds will shut down the UPS. An audible alarm
sounds briefly.
Alarm When a UPS audible alarm is active, pressing and releasing
Silence the main ON/OFF button will silence the active audible
alarm, whether mains power is present or not. Once the
alarm silence function has been activated, all active audible
alarms—except for low battery or overload conditions—will
remain silenced until a new alarm condition is detected.
NOTE
Do not hold ON/OFF button down for more than 2
seconds or the UPS will shut down.
10
Status Indicators: Mains/Battery, Fault
There are two (2) status indicators on the top panel of the UPS, as
shown in the diagram below. Each indicator illuminates to specify the
status of the UPS (see Troubleshooting section for details).
Mains/Battery Indicator (Green)
The Mains/Battery Indicator illuminates when the UPS is operating
in Normal mode, supplying power to connected loads. The Mains/Bat-
tery Indicator flashes when the UPS is operating in Battery mode.
Fault Indicator (Red)
The Fault Indicator illuminates when the UPS detects an internal
fault. It flashes if the UPS detects an overload condition.
Location and Status of Indicators
Mains/Battery Indicator (Green)
Fault Indicator (Red)
11
MODES OF OPERATION
Normal Mode
During Normal mode operation, the Power-
Sure PST supplies conditioned, computer-
grade power to the connected equipment:
mains power passes through the TVSS cir-
cuitry, EMI/RFI filters and then through the
Transfer Switch to the connected equipment.
-
+
Continuous indicator
illumination denotes
Normal Mode
When the UPS is in Normal mode, the
Mains/Battery Indicator illuminates green.
The PowerSure PST continuously monitors the batteries to maintain
them in a fully charged state. The battery charger operates whenever
AC power is present, even if the UPS is switched off. The UPS per-
forms an automatic battery test after it has been operating continu-
ously for two (2) weeks.
Battery Mode
The UPS switches to Battery mode in the
-
+
event of an extreme voltage/frequency condi-
tion or complete mains failure. The battery
system supplies power through the Inverter to
When the UPS is in Battery mode, the Mains/
Battery Indicator flashes green and an alarm
sounds every 5 seconds.
Flashing indicator
illumination denotes
Battery Mode
When a low battery condition occurs, the Battery Indicator continues
to flash green and the alarm sounds every half-second. Low battery
warning is initiated when approximately two (2) minutes of battery
run time are remaining. For more information, refer to Trouble-
shooting section.
CAUTION
!
Turning off the UPS while in either Normal mode or Battery
mode will result in the loss of output power.
NOTE
Once mains power is restored, the UPS resumes normal
operation. At this time, the battery charger begins recharging
the battery. The UPS is capable of OFF-State charging, i.e.,
with mains power, the UPS will charge the batteries as long
as it is plugged in.
12
COMMUNICATIONS
USB Interface Port
The PowerSure PST models with extension “-230U” have a USB inter-
face port for communication that will work with the built-in Microsoft
Power Manager software on the user’s PC, if the PC is so equipped. It
will provide UPS status and manages the automatic, orderly shut-
down of the computer. The UPS (USB) communications meets HID
standard, version 1.11. All USB models are compatible with Microsoft
Windows 2000, Windows XP and Mac OS 10.2 or later. All USB mod-
els ship with a 1.8m (6 ft.) USB cable.
Microsoft, Windows, and the Windows logo
are trademarks, or registered trademarks of
Microsoft Corporation in the United States
and/or other countries.
Data Line Protection Connectors
Data line (1 input & 2 outputs) connectors are located on the rear of
the UPS and provide transient voltage surge suppression (TVSS) for
Phone/Fax/DSL/Internet/Modem devices.
13
MAINTENANCE
The PowerSure PST UPS requires very little maintenance. Follow
these practices to prevent problems.
Cleaning the UPS
The following will help ensure trouble-free operation for years:
• Vacuum dust from the ventilation intake occasionally.
• Wipe the cover periodically with a dry cloth.
Maintaining Batteries
The batteries are valve-regulated, nonspillable, lead acid and must be
kept charged to retain their design life. The UPS continuously charges
the batteries when connected to the mains supply, even while the UPS
is switched off.
When storing the UPS, it is recommended to plug in UPS for at least
24 hours every four to six months to ensure full recharge of the batter-
ies.
14
TROUBLESHOOTING
The information below indicates various symptoms a user may
encounter in the event the PowerSure PST experiences a problem. Use
this information to determine whether external factors caused the
problem. See Troubleshooting Chart for suggested remedy.
1. The Fault Indicator illuminates, indicating
the UPS detected a problem.
2. An alarm sounds, alerting that the UPS
requires attention. The alarm can be
silenced except for low battery and overload
warning conditions.
3. Mains/Battery Indicator may be illuminated
as a diagnostic aid to the operator, as shown
below:
Fault
Indicator
Mains/
Battery
Indicator
Guide to Status Indicators
Fault
(Red)
Mains/Battery
(Green)
Diagnosis/
Audible Alarm
-
+
!
Normal Mode
UPS is operating in Normal Mode; no
beep.
—
—
ON
Battery Test has been initiated; no
beep.
Flashing
ON
The unit is overloaded; beep every
half-second
Flashing
ON
ON
The UPS has failed; continuous beep
Unit has shutdown due to overload;
continuous beep
Flashing
ON
—
—
The UPS shutdown due to failure;
continuous beep
Battery Mode
The UPS is operating in Battery mode;
beep every 5 seconds.
—
—
Flashing
Flashing
Flashing
UPS battery is low; beep every
half-second
The unit is overloaded; beep every
half-second
Flashing
ON
Flashing The UPS has failed; continuous beep
15
Troubleshooting Chart
If the UPS fails to operate properly, turn off the unit and repeat the
steps in the Installation section of this manual. If the problem per-
sists, refer to the chart below:
Problem
Cause
Solution
Check the circuit protector on the side
of the UPS. If it is tripped, reset it and
restart the UPS.
For further help, call your local dealer,
Liebert representative or the Liebert
Worldwide Support Group.
UPS will not
start
Overload/
Short circuit
UPS not plugged in
Plug in power cord securely.
Circuit protector
tripped
Reset the circuit protector and restart
the UPS.
Power not available
at mains receptacle
Have the mains receptacle checked
by a qualified electrician.
UPS starts
on battery,
but will not
switch to AC
Wait until the voltage rises to an
appropriate level or have the mains
receptacle checked by a qualified
electrician.
Input voltage below
threshold
Wait until voltage lowers to an
appropriate level or have the mains
receptacle checked by a qualified
electrician.
AC overvoltage
Overload/
Short circuit
Check the circuit protector on the rear
of the UPS. If it is tripped, reset it and
restart the UPS.
If the problem persists, disconnect
some of the equipment from your
UPS—the total wattage of your
equipment must not exceed the
capacity of the UPS. For further help,
call your local dealer, Liebert
representative or the Liebert
Worldwide Support Group.
UPS shuts
down, Fault
Indicator lit
Internal UPS fault
Overload
Reduce load.
UPS not
providing
expected
backup time
Battery not charged
due to a recent
outage
Recharge battery.
16
SPECIFICATIONS
PA500-230U
PA500-230
PA650-230U
PA650-230
Model Number
Model Rating VA / W
500 / 300
650 / 360
DIMENSIONS: mm (in.)
Unit
W x D x H
168 x 250 x 95
(6.6 x 9.8 x 3.7)
168 x 250 x 95
(6.6 x 9.8 x 3.7)
Shipping
W x D x H
238 x 350 x 142
(9.4 x 13.8 x 5.6)
238 x 350 x 142
(9.4 x 13.8 x 5.6)
WEIGHT: kg (lbs)
Unit
4.7 (10.4)
5.7 (12.5)
5.7 (12.5)
6.7 (14.8)
Shipping
INPUT AC PARAMETERS
Surge Protection
Rated Input Voltage
220J
230VAC
Voltage Range Without
Battery Operation
180VAC - 264VAC (±6VAC)
47 - 63 Hz (±0.4 Hz)
Frequency
OUTPUT AC PARAMETERS
(3) IEC-320-C13 (orange)
battery backup+surge protection
(2) IEC-320-C13 (black)
surge protection
Output Receptacles
2m (6.6 ft) detachable, w/IEC-320 (Wire Type: 1mm2,
H05W-F 3G)
Output Cord
Voltage (Battery Mode)
Output Current
230VAC (±8%)
2.9 A
4.2 A
Waveform (Battery Mode)
Frequency (Battery Mode)
Overload Warning
Stepped Sinewave
50/60 Hz (±1 Hz)
>100%
Overload Shutdown
BATTERY PARAMETERS
Type
>110%
Valve-regulated, nonspillable, lead acid
1 x 12V x 5 Ah 1 x 12V x 7 Ah
Quantity x Voltage x Rating
Transfer Time
4 – 6 ms typical
At 25°C (77°F), resistive loading,
w/ fully charged batteries:
Back-up Time:
Full load
Half load
2 minutes
8 minutes
1 minute
8 minutes
12 hours to 90% rated capacity, after full discharge
into resistive load
Recharge Time
17
ENVIRONMENTAL
Operating Temperature
Storage Temperature
Relative Humidity
Operating Elevation
Audible Noise
AGENCY
0°C to +40°C (+32°F to + 104°F)
-15°C to +50°C (+5°F to + 122°F)
0% to 95%, non-condensing
Up to 3000 m (10,000 ft.) at 35°C (95°F) w/o derating
< 40 dBA, at 1 meter
Safety
EN50091-1-1, TUV/GS listed, CE Compliance Mark
EN61000-4-5, Level 3, Criteria A
Surge
ESD
EN61000-4-2, Level 3, Criteria A
Susceptibility
EN61000-4-3, Level 2, Criteria A
Electrical Fast Transient/
Burst
EN61000-4-4, Level 3, Criteria A
Emissions
EN50091-2, Class B
EN61000-3-2
Harmonics
Conducted Immunity
Flicker
EN61000-4-6
EN61000-3-3
Transportation
ISTA Procedure 1A
Battery Run Times
Load %
5
500VA
650VA
95
53
25
19
12
8
117
73
35
20
12
8
10
20
30
40
50
60
7
7
70
5
4
80
3
3
90
3
2
100
2
1
Note: Approximate discharge times are in minutes and
at 25°C (77°F) with resistive load.
18
POWER AVAILABILITY
PowerSure™ PST
USER MANUAL
Technical Support/Service
The Company Behind the Products
Web Site
Monitoring
800-222-5877
With over a million installations around the globe,
Liebert is the world leader in computer protection
systems. Since its founding in 1965, Liebert has
Outside the US: 614-841-6755
developed
a
complete range of support and
protection systems for sensitive electronics:
Single-Phase UPS
800-222-5877
•
•
•
Environmental systems—close-control air
conditioning from 1 to 60 tons
Power conditioning and UPS with power
ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
Environmental Systems
environmental and power protection in
single, flexible package
a
800-543-2778
Outside the United States
•
•
Monitoring and control—from systems of any
size or location, on-site or remote
Service and support through more than 100
service centers around the world and a 24/7
Customer Response Center
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
While every precaution has been taken to ensure
the accuracy and completeness of this literature,
Liebert Corporation assumes no responsibility and
disclaims all liability for damages resulting from use
of this information or for any errors or omissions.
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
Fax: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
© 2003 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to change without notice.
Hong Kong
+852 2 572 2201
Fax: +852 2 831 0114
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.
SLI-23275 (2/03) Rev. 0
|