ADT Security Services Smoke Alarm Safewatch Pro 2000 User Manual

Security  
Security  
System  
System  
User's Manual  
Safewatch Pro® 2000  
N7527–5V3 Rev. B  
1/01  
Model SAVS20ADT-1 or SAVS20ADTG  
UL File No. S1632  
 
TABLE OF CONTENTS  
SYSTEM OVERVIEW................................................4  
CHIME MODE ..........................................................20  
PANIC KEYS ...........................................................21  
SINGLE-BUTTON PAGING FEATURE.....................22  
USING DEVICE COMMANDS...................................23  
PAGING FEATURE..................................................24  
General....................................................................4  
A Partitioned System ..................................................4  
Zones ......................................................................4  
Burglary Protection ....................................................5  
Security Codes..........................................................5  
Fire Protection...........................................................5  
Alarms .....................................................................5  
Memory of Alarm ........................................................6  
Phone Access & Voice Response Capability....................6  
Paging Feature ..........................................................6  
Single-Button Arming Feature .......................................6  
SECURITY CODES..................................................25  
General...................................................................25  
Babysitter Code........................................................25  
Duress Code............................................................25  
Quick Arming & Single-Button Arming............................25  
To Add or Change A User’s Code..................................26  
To Delete A User.......................................................26  
ENTRY/EXIT DELAYS ..............................................7  
General Information....................................................7  
Exit Alarms ...............................................................8  
TESTING THE SYSTEM...........................................27  
TROUBLE CONDITIONS..........................................29  
COMMON ZONE OPERATION...................................8  
FIRE ALARM SYSTEM.............................................32  
Silencing Fire Alarms .................................................32  
Manually Initiating a Fire Alarm.....................................33  
ABOUT THE TOUCHPADS ........................................9  
General....................................................................9  
2-Line Custom English Display Touchpads ......................9  
English Display Touchpads ..........................................9  
NFPA RECOMMENDATIONS ...................................34  
EMERGENCY EVACUATION ...................................35  
MAINTAINING YOUR SYSTEM................................36  
QUICK GUIDE TO SYSTEM FUNCTIONS................38  
FUNCTIONS OF THE TOUCHPADS......................... 11  
CHECKING FOR OPEN ZONES .............................. 13  
ARMING PERIMETER ONLY (STAY)...................... 14  
ARMING PERIMETER ONLY (INSTANT) ................ 15  
ARMING ALL PROTECTION (AWAY)...................... 16  
DISARMING AND SILENCING ALARMS................. 17  
SUMMARY OF AUDIBLE NOTIFICATIONS..............39  
English Display Touchpads.........................................39  
Custom English Display Touchpads..............................40  
LIMITATIONS OF THE ALARM SYSTEM.................44  
BYPASSING PROTECTION ZONES ....................... 18  
Quick Bypass.......................................................... 19  
LIMITED  
WARRANTY...................................46  
– 3 –  
 
SYSTEM OVERVIEW  
Congratulations on your ownership of an ADT Partitioned Security System. You've made a wise  
decision in choosing it, for it represents the latest in security protection technology today, and  
millions of premises are protected by ADT systems.  
General  
This system offers you three forms of protection: burglary, fire and emergency. Your system  
consists of at least one touchpad which provides control of system operation, and includes  
various sensors which provide perimeter and interior burglary protection, plus smoke or  
combustion detectors designed to provide early warning in case of fire.  
The system uses microcomputer technology to monitor all protection zones and system status,  
display appropriate information on the touchpad(s) used with the system, and initiate  
appropriate alarms. Your system may also have been programmed to automatically send alarm or  
status messages over the phone lines to a Customer Care Center.  
A Partitioned  
System  
Simply stated, a partitioned system is a single physical alarm system that provides independent  
areas of protection intended for use by independent users. For the most part, you need not  
know about other users and their structure in the system, but from time to time, you may see  
display messages which indicate the system is in use by another user; this is normal. A  
partitioned system may also have a "common zone" area, which is an area shared by users of  
both partitions. Refer to the COMMON ZONE OPERATION section for details on using this  
feature.  
Zones  
Your system's sensing devices have been assigned to various "zones." For example, the  
sensing device on your Entry/Exit door may have been assigned to zone 01, sensing devices  
on windows in the master bedroom to zone 02, and so on. These numbers will appear on the  
display, along with a description for that zone (if programmed), when an alarm or trouble  
condition occurs.  
– 4 –  
 
SYSTEM OVERVIEW (Continued)  
Burglary  
Protection  
Your system provides three modes of burglary protection: STAY, AWAY, and INSTANT, and  
allows you to BYPASS selected zones while leaving the rest of the system armed. You must  
turn on or "arm" the burglary protection portion of your system before it will sense burglary  
alarms. The system also provides a CHIME mode, for alerting users to the opening of protected  
doors and windows while the system is disarmed. Refer to the other sections of this manual for  
procedures for using these features.  
The following table lists the four different arming modes and the results of each.  
Features For Each Arming Mode  
Arming  
Mode  
Exit Delay  
Entry Delay  
Perimeter Armed  
Interior Armed  
AWAY  
STAY  
INSTANT  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
No  
No  
Security Codes  
At the time of installation, you were assigned a personal four-digit security code, known only to  
you. You must enter the security code when arming and disarming the system, and when  
performing other system functions. As an additional safety feature, other users who do not have  
a need to know your code can be assigned different security codes. Refer to the SECURITY  
CODES section for procedures on adding security codes to the system.  
The fire protection portion of your security system (if used) is always active and will sound an  
alarm if a fire condition is detected. A key on the touchpad will enable you to manually initiate a  
fire alarm, if necessary. Refer to the FIRE ALARM SYSTEM section for important information  
concerning fire protection, smoke detectors and planning emergency exit routes.  
Fire Protection  
Alarms  
When an alarm occurs, both the touchpad and external sounders will sound, and the touchpad  
will display the zone(s) causing the alarm. If your system is connected to a Customer Care  
Center, an alarm message will also be sent. To stop the alarm sounding, simply disarm the  
system.  
– 5 –  
 
SYSTEM OVERVIEW (Continued)  
Memory of Alarm  
When an alarm condition occurs, the touchpad displays the number(s) of the zone(s) that  
caused the problem, and displays the type of alarm (ex. FIRE, ALARM). It remains displayed until  
it is cleared by disarming the system (see DISARMING THE SYSTEM section).  
Phone Access &  
Voice  
Your system may include a voice module that will permit you to access the system via a Touch-  
tone phone, either on-premises or by call-in when away. The phone access feature will enable  
you to do the following:  
Response  
Capability  
Receive synthesized voice messages over the telephone regarding the status of the  
security system.  
Arm and disarm the system and perform most function commands via the telephone, with  
voice confirmation provided after each command entry.  
Complete information regarding the use of this feature is provided in a separate manual entitled  
PHONE ACCESS USER'S GUIDE, which accompanies the voice module.  
Paging Feature  
If the paging feature has been programmed for your system, a pager will respond to certain  
conditions as they occur in your system. The pager will display code numbers indicating the  
type of condition that has occurred. Refer to the PAGING FEATURE section later in this manual  
for detailed information.  
Single-Button Paging: The touchpads have a special key (identified as the “D” key) which  
may be used to signal a Pager. The message displayed on the pager when this key is pressed is  
999–9999. This code could mean “call home”, “call your office”, or whatever you decide this  
code will mean. See SINGLE-BUTTON PAGING FEATURE section.  
Single-Button  
Arming Feature  
If programmed for your system, keys A and B on the touchpads may have been programmed for  
single-button arming without the use of a security code, as follows:  
Check with your installer  
if single-button arming is  
present in your system.  
Key A, when pressed for 2 seconds, will arm all protection (AWAY mode).  
Key B, when pressed for 2 seconds, will arm the perimeter (STAY mode).  
– 6 –  
 
ENTRY/EXIT DELAYS  
General  
Information  
Your system has preset time delays, known as exit delay and entry delay. Whenever you arm  
your system, exit delay gives you time to leave through the designated exit door without  
setting off an alarm. Exit delay begins immediately after entering any arming command, and  
applies to all modes of arming protection. If programmed, a slow beeping will sound throughout  
the exit delay period.  
Entry Delays give you time to disarm the system when you re-enter through the designated  
entrance door. But you must disarm the system before the entry delay period ends, or an alarm  
will occur. The touchpad beeps during the entry delay period, reminding you to disarm the  
system. There are two entry delays (if programmed). The first is for your primary entrance and  
the second can be used for a secondary entrance, where a longer delay is required to walk to  
the touchpad to disarm the system.  
You can also arm the system with no entry delay at all by using the INSTANT arming mode. This  
mode provides greater security while on the premises or while away for extended periods of  
time.  
See your installer for your delay times.  
Partition 1  
Exit Delay:  
seconds  
Entry Delay 1:  
Entry Delay 2:  
seconds  
seconds  
Partition 2  
Exit Delay:  
seconds  
Entry Delay 1:  
Entry Delay 2:  
seconds  
seconds  
– 7 –  
 
ENTRY/EXIT DELAYS (Continued)  
Exit Alarms  
Whenever you arm the system, the exit delay begins. If an entry/exit door or interior zone is  
faulted when the exit delay ends (e.g., exit door left open), the system sounds an alarm and  
starts the entry delay timer. If you disarm the system before the entry delay ends, the alarm  
sound stops and the message "CANCELED ALARM" or "CA" is displayed on the touchpad,  
along with a zone number indicating the faulted zone. No message is sent to the Customer Care  
Center. To clear the exit alarm condition, the open zone must be made intact; to clear  
the display, enter your code plus OFF.  
If you do not disarm the system before the entry delay ends, and an entry/exit door or interior  
zone is still open, the alarm sound continues and an "exit alarm" message is sent to the  
Customer Care Center. The message ""EXIT ALARM" or "EA" is displayed on the touchpad,  
along with a zone number indicating the faulted zone. To stop the alarm, the system must be  
disarmed (your code plus OFF); to clear the display, enter your code plus OFF a second time.  
To minimize false alarms  
sent to the Customer  
Care Center, your  
system may have been  
programmed for this fea-  
ture. Ask your installer if  
"Exit Alarm" is active for  
your system.  
Exit Alarm Active  
An “exit alarm” also results if an entry/exit door or interior zone is faulted within two minutes after  
the end of the exit delay.  
COMMON ZONE OPERATION  
Your system may have been set up to use a common zone, which is an area shared by users of  
both partitions, such as a foyer or lobby. If so, please note the following:  
Ask your  
installer if a common  
zone was assigned.  
• The common zone will sound and report alarms only when both partitions are armed. If only  
one partition is armed, the system ignores faults on the common zone.  
• Either partition may arm its system if the common zone is faulted, but once armed, the other  
partition will not be able to arm unless the common zone is first bypassed or the fault is  
corrected.  
• If either partition is armed and the other is in chime mode, the common zone will not chime.  
The common zone will chime if both partitions are disarmed and either is in chime mode.  
• Faults on the common zone are displayed on touchpads in both partitions.  
• Either partition can clear and restore the common zone after an alarm.  
– 8 –  
 
ABOUT THE TOUCHPADS  
Your touchpads allow you to control all system functions. The touchpads feature a telephone  
style (digital) touchpad and a Liquid Crystal Display (LCD) which shows the nature and location  
of all occurrences.  
General  
The touchpads also feature a built-in sounder which will sound during alarms and troubles.  
The touchpads also "beep" during certain system functions, such as during entry/exit delay  
times, in CHIME mode, and when depressing any of the keys (to acknowledge the key press).  
IMPORTANT: If the touchpad beeps rapidly upon entering the premises, it indicates that  
an alarm has occurred during your absence and an intruder may still be on the premises.  
LEAVE IMMEDIATELY and CONTACT THE POLICE from a nearby safe location.  
There are two basic types of touchpads – an English display touchpad and a Custom  
English display touchpad (both described below). English display and Custom English  
display touchpads are functionally the same, even though they have different types of  
displays. Both types of touchpads are shown on page 12.  
2-Line Custom 2-line Custom English Display touchpads feature a 2-line, 32-character alphanumeric LCD  
English Display which can display system messages in friendly English. These touchpads can also be  
Touchpads programmed with custom zone descriptors. To access the keys on the touchpad, simply open  
the swing-down door.  
English Display  
Touchpads  
English Display touchpads are functionally identical to Custom English Display touchpads, but  
the LCD display uses pre-designated words to identify the nature and location of  
occurrences. To access the keys on the touchpad, simply open the swing-down door.  
– 9 –  
 
ABOUT THE TOUCHPADS (Continued)  
English Display Touchpad  
AWAY: All burglary zones, interior and perimeter, are armed.  
NO AC  
TEST  
NOT READY  
CHIME BAT  
AWAY  
STAY: Perimeter burglary zones, such as protected windows and  
BYPASS  
doors, are armed.  
STAY  
ALARM  
FIRE  
INSTANT: Perimeter burglary zones armed and entry delay is turned off.  
CHECK INSTANT  
BYPASS: This appears when one or more burglary protection zones  
ENGLISH DISPLAY TOUCHPAD  
have been bypassed.  
NOT READY: Appears when burglary portion of the system is not ready for arming (due to open protection zones).  
The system is ready to arm when this message disappears and the READY indicator light comes on.  
NO AC: Appears when AC power has been cut off. System is operating on backup battery power.  
AC: Appears when AC power is present.  
CHIME: Appears when the CHIME feature is activated.  
BAT: Low battery condition in a wireless sensor (if zone number displayed) or low system battery (if no  
zone number displayed).  
ALARM: Appears when an intrusion has been detected and the system is armed (also appears during a fire  
alarm or audible emergency alarm). Accompanied by the protection zone in alarm.  
CHECK: Appears when a malfunction is discovered in the system at any time or if an open is detected in a  
FIRE zone at any time or a fault in a DAY/NIGHT burglary zone during a disarmed period.  
Accompanied by a display of zone number in trouble.  
FIRE: Appears when a fire alarm is present. Accompanied by a display of the zone in alarm.  
– 10 –  
 
FUNCTIONS OF THE TOUCHPADS  
1. DISPLAY WINDOW.  
9
CHIME KEY: Turns CHIME mode on and off. When  
on, the opening of windows or doors while the system  
is disarmed will sound 3 beeps at the touchpad(s).  
10.  
Custom English Display Touchpads: These 2-line, 32-  
character Liquid Crystal Display (LCD) touchpads display  
protection point identification, system status, and messages.  
English Display Touchpads: Display protection zone  
ID and system status messages using pre-designated words.  
.
11.  
12.  
READY KEY: Used to display all open protection zones  
#
KEY: This key can be used for "Quick Arming" of the  
1
OFF KEY: Disarms burglary portion of the system,  
silences alarms and audible trouble indicators, and  
clears visual display after problem's correction.  
system without use of a security code (if programmed).  
2.  
13. KEYS 0–9 : Used to enter your security code(s).  
14. READY INDICATOR: (GREEN) Lit when the system is  
ready to be armed (no faults present). While the system is  
disarmed, this indicator will go on and off as protection zones  
are closed and opened.  
2
AWAY KEY: Arms the entire burglary system,  
perimeter and interior.  
3.  
4.  
3
STAY KEY: Arms perimeter portion of burglary  
system only. Interior protection is not armed, allowing  
movement within premises without causing alarm.  
15. ARMED INDICATOR: (RED) Lit when the system has been  
armed.  
4
5
This is not a Function key. Used only as a numeric  
key.  
5.  
16. INTERNAL SOUNDER: The built-in sounder mimics the  
alarm sounder during alarms, and will also "beep" during  
certain system functions.  
.
TEST KEY: Tests the system and alarm sounder if  
disarmed. Refer to TESTING THE SYSTEM section for  
test procedures.  
6
17. EMERGENCY (PANIC) KEYS: Keys A, B, and C may all  
have been programmed for emergency functions; however,  
keys A and B may have been programmed for single button  
arming instead. For details, see PANIC KEYS section.  
6
BYPASS KEY: Removes individual protection  
zones from being monitored by the system.  
7.  
8.  
18. KEY D: This key may have been programmed for single-  
button paging (for details, see the SINGLE-BUTTON PAGING  
FEATURE section).  
7
8
INSTANT KEY: Arms in manner similar to STAY  
mode, but without the entry delay feature. Entering via  
the entry/exit door will cause an instant alarm.  
Note: Keys  
1
through  
3
and  
5
through  
9
each  
CODE KEY: Used to assign additional user codes  
9.  
perform their associated companion system functions (OFF,  
AWAY, STAY, etc.) when preceded by an entry of the security  
code (as described later).  
for other users of the system  
.
– 11 –  
 
1
4
15  
14  
1
15  
14  
ARMED  
READY  
ARMED READY  
16  
5
16  
5
4
3
2
3
2
A
B
C
D
1
4
OFF  
2
5
8
0
AWAY  
3
STAY  
6
7
9
A
B
C
D
1
4
OFF  
2
5
8
0
AWAY  
TEST  
3
STAY  
6
7
9
TEST  
6
9
#
BYPASS  
17  
BYPASS  
17  
6
9
#
7
INSTANT  
CODE  
CHIME  
7
INSTANT  
CODE  
CHIME  
10  
10  
READY  
18  
8
READY  
18  
8
12  
13  
11  
12  
13  
11  
English Display Touchpad  
(Touchpads shown without swing-down front door)  
Custom English Display Touchpad  
When entering codes and commands, sequential key depressions must be made  
within 10 seconds of one another. If 10 seconds elapse without a key depression,  
the entry will be aborted and must be repeated from its beginning. Be sure to  
observe this precaution when performing any of the procedures in this  
manual.  
IMPORTANT!  
If you make a mistake while entering a security code, stop, press the [] key,  
and then start over. If you stop in the middle while entering a code, and then  
immediately start the entry over, an erroneous code might be entered.  
– 12 –  
 
CHECKING FOR OPEN ZONES  
Using the Before arming your system, all protected doors, windows and other protection zones  
must be closed or bypassed (see BYPASSING PROTECTION ZONES section), otherwise  
the touchpad will display a "Not Ready" message, and the READY indicator light on your  
touchpad will not be lit. The READY key can be used to display all faulted zones, making it  
easier for you to secure any open zone.  
READY Key  
To display faulted zones, simply press and release the READY [] key (do not enter  
code first).  
Secure or bypass the zones displayed before arming the system.  
The the touchpad’s READY indicator light will come on when all protection zones have  
been either closed or bypassed. The system can then be armed if desired.  
READY  
TO DISPLAY OPEN ZONES, PRESS THE  
KEY.  
TYPICAL DISPLAYS  
INDICATING OPEN PROTECTION ZONE  
(AFTER PRESSING READY KEY)  
TYPICAL DISPLAYS  
WHEN NOT READY TO ARM  
TYPICAL DISPLAYS  
INDICATING "READY TO ARM"  
DI S A R M E D - P RE S S   
TO S HO W F AU LTS  
F A U LT 0 6  
BE D R O O M W I N D O W  
DI S A R M E D  
RE A D Y T O A R M  
***  
***  
CUSTOM DISPLAY TOUCHPAD  
CUSTOM DISPLAY TOUCHPAD  
CUSTOM DISPLAY TOUCHPAD  
AC  
AC  
AC  
06  
NOT READY  
NOT READY  
ENGLISH DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
NOT READY” DISAPPEARS AND THE  
“READY” INDICATOR LIGHT COMES ON  
– 13 –  
 
(With Entry Delay ON)  
ARMING PERIMETER ONLY  
Using the  
STAY Key  
Use this key when staying inside, but expect someone to use an entry/exit door later. It is  
also useful if you are leaving but someone is staying inside (or if you have pets which are  
moving throughout the premises.  
3
1. Enter your security code and press the STAY [3] key. In some systems, pressing  
the “B” key on on the touchpad for 2 seconds will arm the system STAY (no code is  
required). The “B” key may or may not have been programmed for this. Check with  
your installer.  
BEFORE ARMING,  
close all doors and windows  
(see CHECKING FOR OPEN  
ZONES ).  
2. The touchpad beeps three times and displays the armed STAY message (see  
displays below). The red ARMED indicator also lights. Note that there is an exit delay  
in effect before arming actually takes place. See the note below.  
THE STAY MODE ARMS  
THE PERIMETER, BUT  
ALLOWS USE OF THE  
ENTRY/EXIT DOOR.  
PERSONS WITHIN THE  
PREMISES CAN MOVE  
ABOUT FREELY.  
3. After arming, an alarm sounds immediately if a protected perimeter window or non-  
entry/exit door is opened, but you may otherwise move freely within the premises.  
Anyone entering later can enter through an entry/exit door without causing an alarm, but  
they must disarm the system within the entry delay period to avoid sounding an alarm.  
Exit Delay Restart. If you wish to open the entry/exit door to let someone in after  
arming STAY, you can re-start the exit delay at any time – simply press the [] key,  
then let that person in. This avoids having to disarm the system and then re-arm it again.  
Ask your installer if this  
feature is programmed in  
your system. If so, place a  
check in this box.  
Note: When you first arm in the STAY mode, “You may exit now” will be displayed on a Custom  
Display Touchpad during the programmed exit delay. This delay is in effect even when  
arming STAY. When “You may exit now” disappears, the system is fully armed.  
TYPICAL DISPLAYS – “ARMED STAY”  
AC  
AR M E D  
Y OU M AY E X I T NOW  
S TA Y  
***  
***  
STAY  
ENGLISH DISPLAY TOUCHPAD  
CUSTOM DISPLAY TOUCHPAD  
– 14 –  
 
(With Entry Delay OFF)  
ARMING PERIMETER ONLY  
Using the Use this key when staying inside and do not expect anyone to use an entry/exit door.  
CAUTION: Arming the system in this mode will greatly increase the chance of  
7
INSTANT Key  
false alarms. Use extreme care in selecting this mode of arming.  
1. Enter your security code and press the INSTANT [7] key.  
BEFORE ARMING,  
close all doors and windows  
(see CHECKING FOR OPEN  
ZONES )  
2. The touchpad beeps three times and displays the armed message. The red ARMED  
indicator lights. Note that there is an exit delay in effect before arming actually takes  
place. See the note below.  
3. After arming, an alarm sounds immediately if any protected perimeter door or window  
is opened, but you may otherwise move freely throughout the premises.  
THE INSTANT  
MODE  
ARMS THE PERIMETER  
(INCLUDING ENTRY/EXIT  
DOOR), WITH NO ENTRY  
DELAY. PERSONS WITHIN  
THE PREMISES CAN MOVE  
ABOUT FREELY  
An alarm sounds immediately if anyone opens an entry/exit door.  
Exit Delay Restart. If you wish to open the entry/exit door to let someone in after  
arming INSTANT, you can re-start the exit delay at any time – simply press the []  
key, then let that person in. This avoids having to disarm the system and then re-arm it  
again.  
Note: When you first arm the system in the INSTANT mode, “You may exit now” will be displayed  
on the second line of a Custom Display touchpad during the programmed exit delay. This  
delay is in effect in the system even when arming INSTANT. When the exit delay period  
ends, “You may exit now” disappears and the system is fully armed in the INSTANT  
mode.  
Ask your installer if this  
feature is programmed in  
your system. If so, place a  
check in this box.  
TYPICAL DISPLAYS – “ARMED INSTANT”  
AC  
AR M E D IN S T A N T  
Y OU M AY E X I T NOW  
*
*
STAY  
INSTANT  
ENGLISH DISPLAY TOUCHPAD  
CUSTOM DISPLAY TOUCHPAD  
– 15 –  
 
(With Entry Delay ON)  
ARMING ALL PROTECTION  
Using the Use this key when no one will be staying inside.  
2
AWAY Key  
1. Enter your security code and press the AWAY [2] key. In some systems, pressing  
the “A” key on the touchpad for 2 seconds will arm the system AWAY (no code is  
required). The “A” key may or may not have been programmed for this. Check with  
your installer.  
BEFORE ARMING,  
close all doors and windows  
(see CHECKING FOR OPEN  
ZONES )  
2. The touchpad begins beeping and displays the armed AWAY message. The red  
ARMED indicator also lights.  
3. You must leave through an entry/exit door during the exit delay period to avoid  
causing an alarm. The touchpad will beep rapidly during the last 5 seconds of the exit  
delay to warn you that the delay is ending.  
After the exit delay expires, the system arms and will sound an alarm if a protected window  
or non-entry/exit door is opened, or if any movement is detected inside your premises.  
You may re-enter through an entry/exit door, but must disarm the system  
within the entry delay period to avoid an alarm.  
TYPICAL DISPLAYS  
DURING EXIT DELAY  
TYPICAL DISPLAYS AFTER EXIT DELAY  
(SYSTEM FULLY ARMED IN AWAY MODE)  
THE AWAY KEY ARMS THE  
ENTIRE SYSTEM (INTERIOR  
AND PERIMETER), BUT  
ALLOWS USE OF THE  
ENTRY/EXIT DOOR.  
AR M E D  
A W A Y  
AR M E D  
**  
A W A Y  
***  
***  
***  
***  
Y OU M AY E X I T NOW  
AL L S E C U R E  
**  
CUSTOM DISPLAY TOUCHPAD  
CUSTOM DISPLAY TOUCHPAD  
AC  
AC  
AWAY  
AWAY  
ENGLISH DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
16 –  
 
DISARMING AND SILENCING ALARMS  
Using the  
OFF Key  
The OFF key is used to disarm the system, silence alarm and trouble sounds, and clear  
alarm memories. A BURGLARY alarm is a continuous/steady sound from the  
touchpads and any external sounders.  
1
IMPORTANT:  
To Disarm the System  
If you return and the  
main burglary sounder  
is on, DO NOT ENTER, but  
CONTACT THE POLICE from  
a nearby safe location.  
If you return after an alarm  
has occurred and the main  
sounder has shut itself off,  
the touchpad will beep  
Enter your security code and press the OFF key.  
The "Ready" indicator light will be lit if all zones are secure, and the touchpad will emit a  
single tone to confirm that the system is disarmed.  
To Silence a Burglary Alarm  
SEE IMPORTANT NOTE AT LEFT!  
A BURGLARY alarm is a continuous/steady sound.  
Enter your security code and press the OFF key to silence the alarm (or warning tones  
of a Memory of Alarm).  
Note the zone in alarm on the touchpad display, and make that zone intact (close door,  
window, etc.). Now enter the security code plus OFF sequence again to clear the  
touchpad's Memory of Alarm display.  
rapidly  
upon  
your  
entering, indicating that  
an alarm has occurred  
during your absence.  
LEAVE IMMEDIATELY, and  
CONTACT THE POLICE from a  
nearby safe location.  
To Silence a Fire Alarm  
Simply press the OFF key to silence the alarm. Then enter the security code plus  
OFF sequence to clear the touchpad's Memory of Alarm display. See FIRE ALARM  
SYSTEM section.  
TYPICAL BURGLARY ALARM DISPLAY  
AC  
AL A RM 0 6  
BE DR OO M WIN DO W  
06  
ALARM  
CUSTOM DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
– 17 –  
 
BYPASSING PROTECTION ZONES  
Using the This key is used when you want to arm your system with one or more zones intentionally  
unprotected. The system must be disarmed first.  
6
BYPASS Key  
1. Enter your security code and press the BYPASS [6] key.  
LIMITATION  
2. Enter the zone number(s) for the zone(s) to be bypassed (e.g., 06, 10, 13, etc.).  
The system will not allow  
fire zones to be by-  
passed.  
Single digit zone numbers must be preceded by a zero (e.g. 05, 06).  
3. When finished, the touchpad will momentarily display a "Bypass" message for each  
bypassed zone number. Wait for these zones to be displayed, to confirm their  
bypass.  
All bypasses are removed  
when an OFF sequence  
(security code plus OFF)  
is performed.  
4. Arm the system as usual.  
Bypassed zones are unprotected and will not cause an alarm if violated  
while your system is armed.  
TYPICAL MOMENTARY DISPLAYS  
OF BYPASSED ZONE(S)  
TYPICAL DISPLAYS AFTER ALL BYPASSED  
ZONES HAVE BEEN DISPLAYED (PRIOR TO ARMING)  
TO BYPASS ZONES:  
Enter code.  
Press BYPASS key.  
Enter zone Nos.  
Wait for bypassed zones  
to be displayed.  
BY P A S S 0 6  
BE D R O O M W I N D O W  
DI S A R M E D B Y P A S S  
RE A D Y T O A R M  
CUSTOM DISPLAY TOUCHPAD  
CUSTOM DISPLAY TOUCHPAD  
Arm system as usual.  
THE “READY”  
AC  
AC  
INDICATOR WILL  
BYPASS  
BYPASS  
06  
LIGHT TO SIGNIFY  
THAT THE  
SYSTEM IS  
READY TO ARM  
ENGLISH DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
To display bypassed zones prior to arming (see displays above, right), enter your security code and press the  
BYPASS [6] key. This will also bypass any open zones at that time (if “Quick Bypass” is enabled – see following page).  
– 18 –  
 
BYPASSING PROTECTION ZONES (Continued)  
Quick Bypass If your system supports "Quick Bypass", it allows you to easily bypass all open (faulted)  
zones without having to enter zone numbers individually. This feature is useful if, for  
example, you routinely leave certain windows open when arming at night.  
"Quick Bypass" is active  
Ask your installer if  
for your system, and if To use this feature, enter your security code and, within 10 seconds, press the BYPASS  
so, check here:  
[6] key, then stop. In a few moments, all open zones will be displayed along with a  
"Bypass" message. Wait for all bypassed zones to be displayed, then arm the system.*  
*Make sure that only those zones that you wish to leave unprotected are bypassed, and that there  
are no other zones unintentionally left open. This feature will automatically bypass all open zones.  
TYPICAL MOMENTARY DISPLAYS  
OF BYPASSED ZONE(S)  
TYPICAL DISPLAYS AFTER ALL BYPASSED ZONES  
HAVE BEEN DISPLAYED (PRIOR TO ARMING)  
AC  
AC  
BYPASS  
BYPASS  
02  
ENGLISH DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
BY P A S S 0 2  
RE A R D O O R  
DI S A R M E D B Y P A S S  
RE A D Y T O A R M  
CUSTOM DISPLAY TOUCHPAD  
CUSTOM DISPLAY TOUCHPAD  
TYPICAL DISPLAYS AFTER THE SYSTEM IS ARMED WITH BYPASSED ZONES  
AWAY  
AC  
BYPASS  
AR M E D  
Z O N E B Y P A S S E D  
A W A Y  
* **  
***  
CUSTOM DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
– 19 –  
 
CHIME MODE  
Using the Your system can be set to alert you to the opening of a perimeter door or window while it is  
disarmed by using CHIME mode.  
9
CHIME Key  
When activated, three tones will sound at the touchpad whenever a perimeter door or  
window is opened. Interior zones will not produce a tone when they are activated.  
This feature can be used  
only while the burglary Pressing the READY key will display the open protection points.  
system is disarmed.  
To turn Chime Mode on:  
Enter the security code and press the CHIME [9] key. The CHIME message will appear.  
To turn Chime Mode off:  
Enter the security code and press the CHIME [9] key again. The CHIME message will  
disappear.  
TYPICAL DISPLAY WHEN CHIME IS ON  
AC  
DIS AR ME D C HIM E  
RE AD Y TO AR M  
CHIME  
CUSTOM DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
IN CHIME MODE, ANY OPEN PROTECTION POINTS WILL BE DISPLAYED  
WHEN THE “READY” KEY IS PRESSED  
AC  
02  
FA UL T 02  
RE AR D OO R  
NOT READY  
CHIME  
CUSTOM DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
– 20 –  
 
PANIC KEYS  
(FOR MANUALLY ACTIVATING SILENT AND/OR AUDIBLE ALARMS)  
Using Your system may have been programmed to use special keys to manually activate  
Panic Keys emergency (panic) functions. The emergency functions that can be programmed are:  
Silent Emergency, Audible Emergency, Personal Emergency, and Fire.  
Activating a silent emergency sends a silent alarm signal to the Customer Care Center,*  
but there will be no audible alarm or any visual display indicating that a silent alarm has been  
initiated.  
Activating an audible emergency sends a signal to the Customer Care Center* and  
sounds a loud, steady alarm at your touchpad(s) and at any external sounders that may be  
connected (ALARM plus a zone number is also displayed).  
Activating a personal emergency alarm sends an emergency message to the Customer  
Care Center* and sounds at touchpad(s), but not at external bells or sirens.  
*If connected to the  
Customer Care Center.  
Activating a Fire Alarm will send a fire alarm message to the Customer Care Center* and  
will uniquely sound external bells and sirens.  
TYPICAL DISPLAYS WHEN A PANIC KEY THAT HAS BEEN  
PROGRAMMED FOR “AUDIBLE EMERGENCY” IS PRESSED.  
AC  
NOTE: Zone 99 is the zone  
number displayed when an Audible  
Emergency alarm is initiated via a  
Panic key  
9 9  
AL A RM 99  
NOT READY  
ALARM  
CUSTOM DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
To Initiate a Panic  
Function at Any Time  
Press any individual lettered key (A, B,or C) that has been programmed for the desired  
emergency function for at least 2 seconds. See the chart on the next page for  
functions that have been programmed for the various keys in your  
system.  
– 21 –  
 
PANIC KEYS (Continued)  
See your installer and note here any functions programmed for your system.  
CHECK IF  
ACTIVE  
PANIC  
KEY(S)  
ZONE  
PLACE A CHECK NEXT TO PROGRAMMED FUNCTION  
DISPLAY  
[A]  
[B]  
[C]  
9 5 †  
___SILENT, ___AUDIBLE, ___PERSONAL, ___FIRE, ___ARM AWAY*  
9 9 †  
96  
___SILENT, ___AUDIBLE, ___PERSONAL, ___FIRE, ___ARM STAY*  
___SILENT, ___AUDIBLE, ___PERSONAL ___FIRE.  
NOTE: KEY [D] DOES NOT PROVIDE A PANIC FUNCTION (SEE “SINGLE-BUTTON PAGING FEATURE” SECTION BELOW).  
* KEYS [A] AND [B] MAY HAVE BEEN PROGRAMMED FOR SINGLE-BUTTON ARMING INSTEAD OF AN EMERGENCY  
FUNCTION, AS SHOWN.  
THIS ZONE NUMBER NOT DISPLAYED IF KEY HAS BEEN PROGRAMMED FOR SINGLE BUTTON ARMING (ARM-AWAY or  
ARM-STAY)  
SINGLE-BUTTON PAGING FEATURE  
The “D” key on the touchpads can be used to send a signal to a Pager (check if this feature has  
been programmed in your system). The message displayed on the Pager when the “D” key is  
pressed is 999–9999. This code could mean “call home”, “call your office”, or other message. A  
prearranged meaning for this signal should be agreed upon. See the illustration on page 12 for the  
location of the “D” key.  
To send a signal to the Pager, simply press the “D” key for at least 2 seconds. The recipient, on  
seeing the 999–9999 display, will understand the pre-arranged meaning of this signal.  
– 22 –  
 
USING DEVICE COMMANDS  
General  
Information  
Your system may be set up so that certain lights or other devices can be turned on or off by  
using the device command from the touchpad. Ask your installer if this has been done in your  
system. If programmed for your system, some devices may activate automatically upon certain  
system conditions. In this case, the following commands can be used to override the device  
activation. See your installer for a full explanation of this feature.  
To activate  
devices  
ENTER SECURITY CODE THEN PRESS # + 7 + DEVICE NUMBER  
+
#
+ 7 +  
(Security Code)  
(Device Number)  
Example: 7  
2
9
6
then press #, then press 7, then enter the number representing  
the device you wish to activate. See your installer for device numbers assigned for your system.  
To deactivate  
devices  
ENTER SECURITY CODE THEN PRESS # + 8 + DEVICE NUMBER  
+
#
+ 8 +  
(Security Code)  
(Device Number)  
Example:  
7
2
9
6
then press #, then 8, then enter the number representing the  
device you wish to deactivate. See your installer for device numbers assigned for your system.  
Device  
Description  
Device  
Description  
1
2
3
4
5
6
7
8
– 23 –  
 
PAGING FEATURE  
If the paging feature has been programmed, a pager will respond to certain conditions as they occur in your system by  
displaying a 7-digit system status code that will indicate the type of condition that has occurred. In some cases, the 7-  
digit code may be preceded by 16 digits, which can consist of a PIN number, Subscriber account number, or any  
additional data that you may wish to have sent to the pager in addition to the 7-digit system status code.  
The entire pager display format is as follows:  
3-digit Event Code  
Optional 16 digits  
AAAAAAAAAAAAAAAA – BBB – CCCC  
4-digit User or Zone No.  
A = Optional 16-digits for Account numbers, PIN numbers, or any  
other data. This information must be programmed by the  
installer.  
The 3-digit Event Codes (BBB) that can be  
displayed are:  
911 = Alarms. The 4-digit number (CCCC) following this  
B = A 3-digit code that describes the event that has occurred in  
code will be the zone number that has caused the alarm.  
your system (see explanation for event codes on the right).  
811 = Troubles. The 4-digit number (CCCC) following  
this code will be the zone number that has caused the  
trouble.  
C = A 4-digit User or Zone number, depending on the type of event  
that has occurred. For alarms and troubles, these digits  
represent the zone number. For openings (disarming) and  
closings (arming), these digits represent the user number. In  
this system, the first 2 digits will always be “00” (e.g., 0004  
will be displayed for zone number 4). Note that single-digit  
user or zone numbers are always preceded by a zero.  
101 = Open (system disarmed). The 4-digit number  
(CCCC) that follows this code will be the user number.  
102 = Close (system armed). The 4-digit number  
(CCCC) that follows this code will be the user number.  
Examples of typical pager displays follow. Not included in the examples below are the optional 16 digits (preceding the  
7-digit status code) that may have been programmed by the installer for additional data.  
Example 1. Pager displays: 9 1 1 0 0 0 4 =System is reporting an alarm (911) caused by a fault on zone 4 (0004).  
Example 2. Pager displays: 1 0 20 0 0 5 = System is reporting a closing–system arming (102) by user 5 (0005).  
Single-button paging, using the “D” key on the touchpad, is also possible (see SINGLE-BUTTON PAGING FEATURE  
on a previous page).  
– 24 –  
 
SECURITY CODES  
General  
Information  
As an additional safety feature, other users who do not have a need to know your code can be  
assigned different security codes. These secondary users are identified by "user numbers,"  
which are selected when assigning a user's security code. You can assign up 14 additional user  
codes (user numbers 03-16), including the babysitter and duress codes. Note that the master  
(primary) user of the system is the only one who can assign codes to secondary (or temporary)  
users, and is user number 02; user number 01 is reserved for the installer of the system.  
All codes can be used interchangeably when performing system functions (a system armed with  
one user's code can be disarmed by another user's code), with the exception of the babysitter  
code described below.  
Babysitter Code This code can be used to arm the system in assigned partitions, but cannot disarm the system  
unless the system was armed with this code. This code is typically assigned to someone (such  
as a babysitter) who has a need to arm/disarm the system only at certain times. The babysitter  
code is assigned to user 15. The user of this code should not use the “Quick Arming” feature  
described below.  
Duress Code  
This feature is intended for use when you are forced to disarm or arm the system under threat.  
When used, the system will act normally, but can silently notify the Customer Care Center of  
your situation, if that service has been provided. Duress code is assigned to user 16.  
Important: This code is useful only when the system is connected to the Customer Care  
Center.  
Quick Arming  
and  
Single-Button  
Arming  
Note that if "Quick Arming" was programmed by the installer, the  
place of the security code when arming the system.  
If so programmed, the “A” and “B” keys on a touchpad can be used for single-button arming  
AWAY or STAY, respectively. See ARMING ALL PROTECTION and ARMING PERIMETER  
ONLY sections.  
#
key can be pressed in  
The security code must always be used to disarm the system, however.  
– 25 –  
 
SECURITY CODES  
To Add a User or  
Change a User's  
Code  
Important: Temporary users of the system (e.g., babysitters, cleaning staff) should not be shown how  
to use any system function they do not need to know, such as bypassing protection zones for example.  
Sequential key depressions for all steps in a procedure must be made within 2 seconds of one  
another, or else the entire entry is aborted and must be repeated from its beginning (e.g.,  
perform steps 1, 2, and 3 below with no delay between steps).  
CODE  
1.  
+
8
Enter master code, then press CODE key.  
Example: then press the CODE key.  
Changing your  
Master Code  
Follow this procedure:  
(Master Code)  
7
2
9
6
Enter your existing  
2.  
3.  
Enter user number. Enter the 2-digit User Number  
(03-16) for the user you are adding or changing.  
Master code + [8] + [0][2]  
+ new Master code + new  
Master code again.  
(User Number)  
(User's Code)  
Enter user's code.  
Enter the new 4-digit security code for that use  
r.  
CODE  
To Delete a User  
1.  
2.  
+
8
Enter master code, then press CODE key.  
Example: then press the CODE key.  
Enter user number.  
(Master Code)  
(User Number)  
7
2
9
6
Enter the 2-digit User Number (03-16) for the user whose  
code you are deleting.  
3. -----------  
Stop.  
Wait (about 3 seconds) until the touchpad beeps once  
before pressing any other key. The code is automatically  
deleted.  
– 26 –  
 
TESTING THE SYSTEM  
(TO BE CONDUCTED WEEKLY)  
Using the  
TEST Key  
The TEST key puts your system into the Test mode, which allows each protection point to be  
checked for proper operation. The touchpad sounds a single beep every 40 seconds as a  
reminder that the system is in the Test mode.  
5
Note: An alarm message will not be sent to your Customer Care Center during the following  
tests.  
1. DISARM THE SYSTEM. Disarm the system and close all protected windows, doors, etc.  
The READY indicator light should come on if all zones are intact (i.e., all protected windows,  
doors, etc. are closed.  
AC  
D IS A R M E D  
RE A D Y T O A R M  
***  
***  
CUSTOM DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
TEST  
2.  
+
5
Enter the security code, then press TEST key.  
(Security Code)  
Example:  
7
2
9
6
then press the TEST key.  
3. Listen. The external sounder should sound for 1 second and then turn off.  
If the sounder does not sound, CALL FOR SERVICE IMMEDIATELY.  
4. Fault zones. Open each protected door and window in turn and listen for three beeps  
from the touchpad. Identification of each faulted protection point should appear on the  
display. The display will clear when the door or window is closed.  
(Continued)  
– 27 –  
 
TESTING THE SYSTEM  
(CONTINUED)  
Walk in front of any interior motion detectors (if used) and listen for three beeps. The  
identification of the detector should appear on the display when it is activated. The display  
will clear when no motion is detected. Note that if wireless motion detectors are used, there  
is a 3-minute delay between activations. This is to conserve battery life.  
To test all smoke detectors, follow the manufacturer's instructions. The identification of  
each detector should appear on the display when each is activated.  
If a problem is experienced with any protection point (no confirming sounds, no display),  
CALL FOR SERVICE IMMEDIATELY.  
When all protection points have been checked and are intact (closed), there should be no  
zone identification numbers displayed on the touchpad.  
When testing is completed, exit the TEST mode by continuing with step 5.  
OFF  
5.  
+
1
Exit test mode.  
(Security Code)  
Enter your security code and press the OFF key.  
If the test mode is inadvertently left active, it automatically  
turns off after 4 hours.  
– 28 –  
 
TROUBLE CONDITIONS  
"Check" and The word CHECK on the touchpad's display, accompanied by a "beeping" at the  
"Battery" Displays  
touchpad, indicates a trouble condition in the system.  
To silence the beeping for these conditions, press any key.  
1. A display of "CHECK" and one or more zone numbers indicates that a  
problem exists with the displayed zone(s) and requires your attention. Determine if  
the zone(s) displayed are intact and make them so if they are not. If the problem has  
been corrected, the display can be cleared if you enter the OFF sequence (security  
code plus OFF key) twice. If the display persists, CALL FOR SERVICE.  
Note: A display of CHECK 70 on English Display touchpads indicates that the  
wiring connection to the external sounder is at fault (opened or shorted), and you  
should CALL FOR SERVICE. See “BELL FAILURE” on next page. A display of  
CHECK 90 indicates that RF interference may be impeding the operation of wireless  
sensors* in the system. See “Rcvr Jam” on next page.  
* Not all systems use  
wireless sensors.  
2. If there are wireless sensors* in your system, the CHECK condition may  
also be caused by some change in the environment that prevents the wireless  
receiver from hearing a particular sensor. CALL FOR SERVICE if this occurs.  
IF YOU CANNOT CORRECT A "CHECK" DISPLAY, CALL FOR SERVICE AT ONCE.  
TYPICAL "CHECK" DISPLAYS  
AC  
06  
C H E C K 0 6  
BE D R O O M W I N D O W  
CHECK  
ENGLISH DISPLAY TOUCHPAD  
CUSTOM ENGLISH DISPLAY  
– 29 –  
 
TROUBLE CONDITIONS (Continued)  
Words or letters in parentheses ( ) are those that are displayed on English Display  
Touchpads  
.
Other Trouble  
Displays  
1. COMM. FAILURE  
(or FC)  
Indicates that a failure has occurred in the telephone com-  
munication portion of your system.  
CALL FOR SERVICE IMMEDIATELY.  
* Any “beeping” that  
accompanies a  
trouble display can be  
stopped by depress-  
ing any key on the  
touchpad or by  
entering an OFF  
sequence (code +  
OFF)  
2. SYSTEM LO BAT  
(or BAT with no zone No.)  
Indicates that a low system battery condition exists. Display  
is accompanied by "beeping"* at the Touchpad. If this  
condition persists for more than one day (with AC present),  
CALL FOR SERVICE.  
3. LO BAT + zone descriptor Indicates that there is alow battery condition in the wireless  
(or BAT with zone No.)  
transmitter**number displayed. Accompanied by a single  
*
"beep" (once every 40 seconds) at the Touchpad.  
Either replace the battery yourself, or CALL FOR SERVICE.  
If the battery is not replaced within 30 days, a CHECK  
display may occur.  
** Not all systems use  
wireless sensors.  
4. Rcvr Jam  
Wireless part of the system is experiencing RF interference  
which may impede reception from wireless sensors.**  
(or CHECK 90)  
5. MODEM COMM  
(or CC)  
Indicates that the control is on-line with the Customer Care  
Center's remote computer. The control will not operate  
while on-line. Wait a few minutes. Display should disappear.  
6. BELL FAILURE  
(or CHECK 70)  
Indicates that the wiring connection to the external sounder  
is at fault (open or shorted). Accompanied by “beeping” at  
the touchpad. CALL FOR SERVICE IMMEDIATELY.  
– 30 –  
 
TROUBLE CONDITIONS (Continued)  
7. AC LOSS is displayed  
(or NO AC)  
The system is operating on battery power only due to an  
power failure.  
Other Trouble  
Displays  
AC  
(Continued)  
If only some lights are out on the premises, check circuit  
breakers and fuses and reset or replace as necessary.  
If AC power cannot be restored and a “low system battery”  
message appears (see item 2 on the previous page),  
CALL FOR SERVICE .  
8. Busy-Standby  
(or dI)  
If this remains displayed for more than 1 minute, system is  
disabled. CALL FOR SERVICE IMMEDIATELY.  
9. OPEN CIRCUIT  
(or OC)  
The touchpad is not receiving signals from the control.  
CALL FOR SERVICE.  
10. Long Rng Trbl  
(or bF)  
If part of your system, back-up Long Range Radio com-  
munication has failed. CALL FOR SERVICE.  
Total Power Failure  
If there is no touchpad display at all, and the READY indicator is not lit,  
operating power (from AC and back-up battery) for the system has stopped and the  
system is inoperative. CALL FOR SERVICE IMMEDIATELY.  
In The Event Of Telephone Operational Problems  
In the event of telephone operational problems, disconnect the control from the phone line by removing the plug from  
the phone wall jack. We recommend that your installer demonstrate this disconnection on installation of the system. Do  
not attempt to disconnect the phone connection inside the control. Doing so will result in the loss of your phone lines. If  
the regular phones work correctly after the control has been disconnected from the phone wall jack, the control has a  
problem and you should immediately call for service. If upon disconnection of the control, there is still a problem on the  
phone line, notify the telephone company that they have a problem and request prompt phone repair service. The user  
may not under any circumstances attempt any service or repairs to the security system. Repairs must be made only by  
ADT authorized service (see the LIMITED WARRANTY statement for information on how to obtain service).  
– 31 –  
 
FIRE ALARM SYSTEM (IF INSTALLED)  
General  
Your fire alarm system (if installed) is on 24 hours a day, for continuous protection. In the  
event of an emergency, the strategically located smoke and heat detectors will  
automatically send signals to your system, triggering a loud, interrupted pulsed sound*  
from the Touchpad(s). This sound will also be produced by any external sounders. A FIRE  
message will appear at your Touchpad and remain on until you silence the alarm (see  
below for silencing fire alarms).  
* Temporal pulse sounding is produced for Fire alarms, as follows:  
3 pulsespause3 pulsespause3 pulses–pause. . . , repeated.  
TYPICAL FIRE EMERGENCY DISPLAYS  
AC  
F IR E 0 5 M A S TE R  
BE D R O O M  
05  
ALARM  
FIRE  
CUSTOM DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
Silencing 1. You can silence the alarm at any time by pressing the OFF key (the security code is  
Fire Alarms  
not needed to silence fire alarms). To clear the display, enter your code and press the  
OFF key again (to clear Memory of Alarm).  
2. If the Touchpad's FIRE display does not clear after the second OFF sequence, smoke  
detectors may still be responding to smoke or heat producing objects in their vicinity.  
Investigate, and should this be the case, eliminate the source of heat or smoke.  
3. If this does not remedy the problem, there may still be smoke in the detector. Clear it  
by fanning the detector for about 30 seconds.  
4. When the problem has been corrected, clear the display by entering your code and  
pressing the OFF key.  
–32–  
 
FIRE ALARM SYSTEM (Continued)  
Manually Initiating 1. Should you become aware of a fire emergency before your detectors sense the  
a Fire Alarm  
problem, go to your nearest Touchpad and manually initiate an alarm by pressing the  
panic key assigned for FIRE emergency for 2 seconds. Check below, and in the  
PANIC KEYS section.  
2. Evacuate all occupants from the premises.  
3. If flames and/or smoke are present, leave the premises and notify your local Fire  
Department immediately.  
4. If no flames or smoke are apparent, investigate the cause of the alarm. The zone  
number(s) of the zone(s) in an alarm condition will be displayed at the Touchpad.  
Panic Key Assigned The “A” key has been assigned for manually initiating a FIRE alarm.  
for FIRE Emergency  
Important: Verify this with your installer.  
Press  
A
for 2 seconds.  
DISPLAYS FOLLOWING MANUAL INITIATION OF A FIRE ALARM  
AC  
F IR E 9 5  
95  
ALARM  
FIRE  
CUSTOM DISPLAY TOUCHPAD  
ENGLISH DISPLAY TOUCHPAD  
– 33 –  
 
NATIONAL FIRE PROTECTION ASSOCIATION  
RECOMMENDATIONS ON SMOKE DETECTORS  
With regard to the number and placement of  
smoke/heat detectors, we subscribe to the  
recommendations contained in the National  
Fire Protection Association's National Fire  
Alarm Code (NFPA 72) noted below.  
KITCHEN  
KITCHEN  
BDRM  
DINING  
BEDROOM  
BEDROOM  
TV ROOM  
DINING  
BDRM  
LIVING ROOM  
Early warning fire detection is best achieved  
by the installation of fire detection equipment  
in all rooms and areas of the household as  
follows:  
BEDROOM  
BEDROOM  
LIVING ROOM  
Smoke Detectors for Minimum Protection  
Smoke Detectors for Additional Protection  
Heat-Activated Detectors  
A smoke detector installed outside of each  
separate sleeping area, in the immediate  
vicinity of the bedrooms and on each  
additional story of the family living unit,  
including basements and excluding crawl  
spaces and unfinished attics.  
BEDROOM  
BEDROOM  
BEDROOM  
TO  
BR  
In addition, the NFPA recommends that you  
install heat or smoke detectors in the living  
room, dining room, bedroom(s), kitchen,  
hallway(s), attic, furnace room, utility and  
storage rooms, basements and attached  
garages.  
KTCHN  
GARAGE  
CLOSED  
DOOR  
LVNG RM  
.
BASEMENT  
–34–  
 
EMERGENCY EVACUATION  
Steps to Safety  
Establish and regularly practice a plan of escape in the event of fire. The following  
steps are recommended by the National Fire Protection Association:  
1. Plan on your detector or your interior and/or exterior sounders warning all  
occupants.  
CLOSET  
BEDROOM  
2. Determine two means of escape from each room. One path of escape should  
lead to the door that permits normal exit from the building. The other may be a  
window, should your path be unpassable. Station an escape ladder at such  
windows if there is a long drop to the ground.  
TH  
BA  
BEDROOM  
BEDROOM  
2ND FLOOR  
KITCHEN  
BACK DOOR  
BEDROOM  
3. Sketch a floor plan of the building. Show windows, doors, stairs and rooftops that  
can be used to escape. Indicate escape routes for each room. Keep these routes  
free from obstruction and post copies of the escape routes in every room.  
TH  
BA  
BEDROOM  
1ST FLOOR  
4. Make sure that all bedroom doors are shut while you are asleep. This will prevent  
deadly smoke from entering while you escape.  
5. Try the door. If the door is hot, check your alternate escape route. If the door is  
cool, open it cautiously. Be prepared to slam the door if smoke or heat rushes in.  
6. In smoky areas, crawl close to floor, hold your breath, and/or cover mouth and  
nose with a wet cloth.  
BACK  
7. Escape quickly; don't panic.  
8. Establish a common meeting place outdoors, away from your premises, where  
everyone can meet and then take steps to contact the authorities and account for  
those missing. Choose someone to assure that nobody returns to the premises  
— many die going back  
FRONT  
–35–  
 
MAINTAINING YOUR SYSTEM  
Taking Care of  
Your System  
The components of your security system are designed to be as maintenance-free as possible.  
However, to make sure that your system is in reliable working condition.  
1. Test your system weekly.  
2. Test your system after any alarm occurs (see TESTING THE SYSTEM).  
Silencing Low  
Battery Warning  
Tones at the  
Touchpad  
You can silence the touchpad’s warning tones by pressing the OFF key, but the touchpad's  
low battery message display will remain on as a reminder that you have a low battery condition in  
one or more of your sensors. When you replace the weak battery with a fresh one, the sensor  
will send a "good battery" signal to the control as soon as the sensor is activated  
(opening/closing of door, window, etc.), causing the low battery display to turn off. If the sensor  
is not activated, the display will automatically clear within approximately 1 hour.  
Replacing  
Batteries in  
Wireless  
Each wireless sensor in your system has a 9-volt or 3-volt battery. The system detects a low  
battery in any wireless sensor, including smoke detectors, the optional personal emergency  
transmitter, and the optional portable wireless touchpad. (A low battery in a portable wireless  
touchpad is detected as soon as one of its keys is pressed, and the wired touchpad will display  
00”.)  
Sensors  
Wireless sensors  
may not have been  
used in your  
Alkaline batteries provide a minimum of 1 year of operation, and in most units and applications,  
provide 2–4 years of service. 3-volt lithium batteries provide up to 4 or more years of operation.  
Actual battery life will depend on the environment in which the sensor is used, the number of  
signals that the transmitter in the sensor has had to send, and the specific type of sensor.  
Factors such as humidity, high or low temperatures or large swings in temperature, may all lead  
to the reduction of actual battery life in an installation.  
security system  
If you have a low battery in a wireless sensor, a low battery message i s  
displayed on the touchpad.  
– 36 –  
 
MAINTAINING YOUR SYSTEM (Continued)  
In addition, a battery-operated smoke detector with a low battery also emits a single "chirp"  
sound approximately once every 20–30 seconds, identifying itself as the smoke detector with  
the weak battery.  
Note: The low battery message comes on as a warning that battery replacement in indicated  
sensor(s) is due within 30 days. In the meantime, a sensor causing a low battery indication is still  
fully operational.  
Important: Use only batteries recommended by your installer as replacement.  
Routine Care  
Treat the components of your security system as you would any other electrical equipment.  
Do not slam sensor-protected doors or windows.  
Keep dust from accumulating on the touchpad and all protective sensors, particularly on  
motion sensors and smoke detectors.  
The touchpad and sensors should be cleaned carefully with a dry soft cloth. Do not spray  
water or any other fluid on the units.  
– 37 –  
 
QUICK GUIDE TO SYSTEM FUNCTIONS  
FUNCTION  
Check Zones  
Arm System  
PROCEDURE  
Press READY key.  
COMMENTS  
To view faulted zones when system not ready.  
Arms system in mode selected.  
Enter code. Press arming key desired:  
(AWAY, STAY, INSTANT)  
Press #. Press arming key desired:  
(AWAY, STAY, INSTANT)  
Quick Arm  
(if programmed)  
Bypass Zone(s)  
Arms system in mode selected, quickly and without use of code.  
Enter code. Press BYPASS key.  
Enter zone number(s) to be bypassed  
(use 2-digit entries).  
Bypassed zones are unprotected and will not cause an alarm if violated.  
Quick Bypass  
Enter code. Press BYPASS key.  
Bypasses all faulted zones automatically.  
(if programmed)  
Silence Sounders  
Burglary:  
Fire:  
Enter code. Press OFF key.  
Press OFF key.  
Press any key.  
Also disarms system. Memory of alarm remains until cleared.  
Memory of Alarm remains until cleared.  
Determine cause.  
"Check":  
Disarm System  
Enter code. Press OFF key.  
After disarming, enter code again.  
Press OFF key again.  
Also silences sounders. Memory of alarm remains until cleared.  
Clear Alarm Memory  
Touchpad will beep rapidly upon entry if alarm has occurred.  
Alarm display will remain upon disarming until cleared.  
Duress (if active  
and connected to  
Customer Care Center)  
Arm or disarm "normally", but  
use your 4-digit Duress code to do so.  
Performs desired action and sends silent alarm to Customer Care Center.  
Panic Alarms  
(as programmed)  
Press key [A], [B], or [C] for at least 2 seconds.  
See the PANIC KEYS section for functions programmed for your system.  
Keys “A” and “B” may have been programmed for single-button arming  
(see ARMING PERIMETER ONLY and ARMING ALL PROTECTION  
sections).  
Chime Mode  
Test Mode  
To turn ON or OFF: Enter code. Press CHIME key. Touchpad will sound if doors or windows are violated while system is  
disarmed and chime mode is ON.  
To turn ON: Enter code. Press TEST key.  
To turn OFF: Enter code. Press OFF key.  
Tests alarm sounder and allows sensors to be tested.  
Phone Access  
(Smartphone Module)  
if applicable  
Consult Phone Access User's Guide that  
accompanies the Phone Module.  
Permits system access remotely, via Touch-tone phone (see pages 6).  
– 38 –  
 
SUMMARY OF AUDIBLE/VISUAL NOTIFICATIONS  
(ENGLISH DISPLAY TOUCHPADS)  
SOUND  
CAUSE  
DISPLAY  
FIRE ALARM  
FIRE is displayed; zone number of zone in alarm is displayed. If a fire alarm is  
manually activated, zone number 95 will be displayed.  
*
LOUD, INTERRUPTED  
Touchpad & External  
BURGLARY/AUDIBLE  
EMERGENCY ALARM  
a. SYSTEM DISARM  
b. SYSTEM ARMING ATTEMPT  
WITH AN OPEN ZONE.  
ALARM is displayed. Zone number of zone in alarm is also displayed.  
*
LOUD, CONTINUOUS  
Touchpad & External  
ONE SHORT BEEP  
(not repeated)  
Touchpad only  
a. READY indicator light comes on.  
b. The number of the open protection zone is displayed.  
c. Zone numbers of the bypassed protection zones are displayed (one beep is  
heard for each zone displayed). Subsequently, BYPASS is displayed.  
c. BYPASS VERIFY  
ONE SHORT BEEP  
(once every 40 seconds)  
Touchpad only  
a. SYSTEM IS IN TEST MODE  
b. LOW BATTERY AT A  
TRANSMITTER  
a. Opened zone numbers will appear.  
b. BAT displayed with zone number of transmitter.  
TWO SHORT BEEPS  
Touchpad only  
ARM AWAY  
AWAY is displayed. Red ARMED indicator is lit.  
THREE SHORT BEEPS  
Touchpad only  
a. ARM STAY OR INSTANT  
a. STAY or INSTANT is displayed. Red ARMED indicator is lit.  
b. ZONE OPENED WHILE SYSTEM  
IS IN CHIME MODE.  
b. CHIME displayed; zone number of open protection zone will be displayed if the  
[] key is pressed.  
RAPID BEEPING  
Touchpad only  
a. TROUBLE  
a. CHECK displayed. Zone number of troubled protection zone is displayed.  
b. FIRE or ALARM is displayed; zone number of zone in alarm is displayed  
c. BAT displayed with no zone ID number.  
b. MEMORY OF ALARM  
c. SYSTEM LOW BATTERY  
d. EXT. SOUNDER WIRING FAIL.  
d. CHECK 70 is displayed.  
SLOW BEEPING  
Touchpad only  
a. EXIT DELAY WARNING (if  
programmed)  
a. AWAY is displayed.  
b. Exceeding the entry delay time without disarming causes alarm.  
b. ENTRY DELAY WARNING  
*
If a bell is used as external sounder, fire alarm is pulsed ring; burglary/audible emergency is steady ring.  
– 39 –  
 
SUMMARY OF AUDIBLE/VISUAL NOTIFICATIONS  
(CUSTOM ENGLISH DISPLAY TOUCHPADS)  
SOUND  
CAUSE  
DISPLAY  
LOUD, INTERRUPTED*  
Touchpad & External  
FIRE ALARM.  
FIRE is displayed; descriptor of zone in alarm is displayed. If a fire alarm is  
manually activated, zone number 95 will be displayed.  
LOUD, CONTINUOUS*  
Touchpad & External  
BURGLARY/AUDIBLE  
EMERGENCY ALARM.  
ALARM is displayed. If programmed, descriptor of zone in alarm is also displayed  
ONE SHORT BEEP  
(not repeated)  
Touchpad only  
a. SYSTEM DISARM.  
b. SYSTEM ARMING ATTEMPT  
WITH AN OPEN ZONE..  
a. DISARMED/READY TO ARM is displayed.  
b. The number and descriptor of the open protection zone is displayed.  
c. BYPASS VERIFY.  
c. Numbers and descriptors of the bypassed protection zones are displayed (One  
beep is heard for each zone displayed). Subsequently, the following is displayed:  
DISARMED BYPASS Ready to Arm.  
ONE SHORT BEEP  
a. SYSTEM IS IN TEST MODE.  
b, LOW BATTERY AT A  
TRANSMITTER.  
a. Opened Zone identifications will appear.  
(once every 40 seconds)  
b. LO BAT displayed with description of transmitter.  
Touchpad only  
TWO SHORT BEEPS  
Touchpad only  
ARM AWAY.  
ARMED AWAY displayed. Red ARMED indicator lit.  
THREE SHORT BEEPS  
Touchpad only  
a. ARM STAY OR INSTANT.  
b. ZONE OPENED WHILE SYSTEM  
IS IN CHIME MODE.  
a. ARMED STAY or ARMED INSTANT displayed. Red ARMED indicator lit.  
b. CHIME displayed, descriptor of open protection zone will be displayed if the []  
key is pressed.  
RAPID BEEPING  
Touchpad only  
a. TROUBLE.  
a. CHECK displayed. Descriptor of troubled protection zone is displayed.  
b. FIRE or ALARM is displayed; descriptor of zone in alarm is displayed.  
c. SYSTEM LO BAT displayed.  
b. MEMORY OF ALARM.  
c. SYSTEM LOW BATTERY.  
d. EXT. SOUNDER WIRING FAIL.  
d. BELL FAILURE is displayed.  
SLOW BEEPING  
Touchpad only  
a. EXIT DELAY WARNING (if  
programmed).  
b. ENTRY DELAY WARNING.  
a. ARMED AWAY is displayed along with You May Exit Now.  
b. DISARM SYSTEM OR ALARM WILL OCCUR is displayed. Exceeding the  
delay time without disarming causes alarm.  
* If a bell is used as external sounder, fire alarm is pulsed ring; burglary/audible emergency is steady ring.  
– 40 –  
 
UL NOTICE: This is a "Grade A" Residential System.  
FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENT  
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the  
following statement for your information:  
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict  
accordance with the manufacturer's instructions, may cause interference to radio and television reception. It has  
been type tested and found to comply with the limits for a Class B computing device in accordance with the  
specifications in Part 15 of FCC Rules, which are designed to provide reasonable protection against such  
interference in a residential installation. However, there is no guarantee that interference will not occur in a particular  
installation. If this equipment does cause interference to radio or television reception, which can be determined by  
turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the  
following measures:  
If using an indoor antenna, have a quality outdoor antenna installed.  
Reorient the receiving antenna until interference is reduced or eliminated.  
Increase the separation between the radio or television receiver and the alarm control.  
Move the antenna leads away from any wire runs to the alarm control.  
Plug the radio or television receiver into a different outlet so that they are on different branch circuit than the alarm  
control.  
If necessary, the user should consult the dealer or an experienced radio/television technician for additional  
suggestions. The user or installer may find the following booklet prepared by the Federal Communications  
Commission helpful: "Interference Handbook". This booklet is available from the U.S. Government Printing Office,  
Washington, DC 20402.  
The user shall not make any changes or modifications to the equipment unless authorized by the Installation  
Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the  
equipment.  
– 41 –  
 
FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 68 STATEMENT  
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains,  
among other information, the FCC registration number and ringer equivalence number (REN) for this equipment. If  
requested, this information must be provided to the telephone company.  
This equipment uses the following jacks: An RJ31X is used to connect this equipment to the telephone network.  
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive  
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all  
areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be  
connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum  
REN for the calling area.  
If this equipment causes harm to the telephone network, the telephone company will notify you in advance that  
temporary discontinuance of service may be required. If advance notice is not practical, the telephone company will  
notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you  
believe necessary.  
The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect  
the operation of the equipment. If this happens, the telephone company will provide advance notice in order for you to  
make the necessary modifications in order to maintain uninterrupted service.  
If trouble is experienced with this equipment, please contact the manufacturer for repair and warranty information. If  
the trouble is causing harm to the telephone network, the telephone company may request you remove the equipment  
from the network until the problem is resolved.  
There are no user serviceable components in this product, and all necessary repairs must be made by the  
manufacturer. Other repair methods may invalidate the FCC registration on this product.  
This equipment cannot be used on telephone company-provided coin service. Connection to Party Line Service is  
subject to state tariffs.  
This equipment is hearing-aid compatible.  
When programming or making test calls to an emergency number, briefly explain to the dispatcher the reason for the  
call. Perform such activities in the off-peak hours; such as early morning or late evening.  
– 42 –  
 
CANADIAN DEPARTMENT OF COMMUNICATIONS (DOC) STATEMENT  
NOTICE  
AVIS  
The Canadian Department of Communications label identifies  
certified equipment. This certification means that the equipment  
meets certain telecommunications network protective, operational  
and safety requirements. The Department does not guarantee the  
equipment will operate to the user's satisfaction.  
L'étiquette du ministère des Communications du Canada identifie le matériel  
homologué. Cette étiquette certifie que le matériel est conforme à certaines normes  
de protection, d'exploitation et de sécurité des réseaux de télécommunications. Le  
ministère n'assure toutefois pas que le matériel fonctionnera à la satisfaction de  
l'utilisateur.  
Avant d'installer ce matériel, l'utilisateur doit s'assurer qu'il est permis de le  
raccorder aux installations de l'entreprise locale de télécommunications. Le matériel  
doit également être installé en suivant une méthode acceptée de raccordement. Dans  
certains cas, les fils intérieurs de l'entreprise utilisés pour un service individuel à la  
ligne unique peuvent être prolongés au moyen d'un dispositif homologué de  
raccordement (cordon prolongateur téléphonique interne). L'abonne ne doit pas  
oublier qu'il est possible que la conformité aux conditions énoncées ci-dessus  
n'empèche pas la dégradation du service dans certaines situations. Actuellement, les  
entreprises de télécommunications ne permettent pas que l'on raccorde leur  
matériel aux prises d'abonnés, sauf dans les cas precis prévus par les tarifs  
particuliers de ces entreprises.  
Before installing this equipment, users should ensure that it is  
permissible to be connected to the facilities of the local  
telecommunications company. The equipment must also be installed  
using an acceptable method of connection. In some cases, the  
company's inside wiring associated with a single line individual  
service may be extended by means of certified connector assembly  
(telephone extension cord). The customer should be aware that  
compliance with the above conditions may not prevent degradation of  
service in some situations.  
Repairs to certified equipment should be made by an authorized  
Canadian maintenance facility designated by the supplier. Any  
repairs or alterations made by the user to this equipment, or  
equipment malfunctions, may give the telecommunications company  
cause to request the user to disconnect the equipment.  
Les réparations du matériel homologué doivent être effectuées pas un centre  
d'entretien canadien autorisé désigné par le fournisseur. La compagnie de  
télécommunications peut demander à l'utilisateur de débrancher un appareil à la  
suite de réparations ou de modifications effectuées par l'utilisateur ou à cause de  
mauvais fonctionnement.  
Users should ensure for their own protection that the electrical  
ground connections of the power utility, telephone lines and internal  
metallic water pipe system, if present, are connected together. This  
precaution may be particularly important in rural areas.  
Pour sa propre protection, l'utilisateur doit s'assurer que tous les fils de mise en  
terre de la source d'énergie électrique, des lignes téléphoniques de réseau de  
conduites d'eau, s'il y en a, soient raccordés ensemble. Cette précaution est  
particulièrement importante dans les régions rurales.  
Caution: User should not attempt to make such connections  
themselves, but should contact the appropriate electric inspection  
authority, or electrician, as appropriate.  
Avertissement: L'utilisateur ne doit pas tenter de faire ces raccordements lui-  
même; il doit avoir recours à un service d'inspection des installations électriques, ou  
à un électricien, selon le cas.  
The Load Number (LN) assigned to each terminal device denotes  
the percentage of the total load to be connected to a telephone loop  
which is used by the device, to prevent overloading. The termination  
on a loop may consist of any combination of devices subject only to  
the requirement that the total of the Load Numbers of all the devices  
does not exceed 100.  
L'indice de charge (IC) assigné à chaque dispositif terminal pour éviter toute  
surcharge indique le pourcentage de la charge totale qui peut être raccordé à un  
circuit téléphonique fermé utilisé par ce dispositif. La terminaison du circuit fermé  
peut être constituée de n'importe quelle combinaison de dispositifs, pourvu que la  
somme des indices de charge de l'ensemble des dispositifs ne dépasse pas 100.  
– 43 –  
 
WARNING!  
THE LIMITATIONS OF THIS ALARM SYSTEM  
While this system is an advanced design security system, it does not offer guaranteed protection against burglary or other  
emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of  
reasons. For example:  
• Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor  
or disconnect an alarm warning device.  
• Intrusion detectors (e.g. passive infrared detectors), smoke detectors, and many other sensing devices will not work  
without power. Battery operated devices will not work without batteries, with dead batteries, or if the batteries are not put  
in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.  
• Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if  
the signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the  
path.  
• A user may not be able to reach a panic or emergency button quickly enough.  
• While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not  
activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the  
Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System  
may not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may  
not sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other  
side of closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second  
floor detector, for example, may not sense a first floor or basement fire. Moreover, smoke detectors have sensing  
limitations. No smoke detector can sense every kind of fire every time. In general, detectors may not always warn about  
fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper  
storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Depending upon  
the nature of the fire and/or the locations of the smoke detectors, the detector, even if it operates as anticipated, may not  
provide sufficient warning to allow all occupants to escape in time to prevent injury or death.  
• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation  
manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of  
protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect  
motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows.  
(Continued)  
– 44 –  
 
WARNING!  
THE LIMITATIONS OF THIS ALARM SYSTEM  
(continued)  
Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical  
system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the  
ambient temperature of protected area approaches the temperature range of 90° to 105°F, the detection performance can  
decrease.  
• Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the  
other side of closed or partly open doors. If warning devices sound on a different level of the residence from the  
bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not  
hear the warning if the alarm is muffled from a stereo, radio, air conditioner or other appliance, or by passing traffic.  
Finally, alarm warning devices, however loud, may not warn hearing-impaired people or waken deep sleepers.  
• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or  
temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.  
• Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect  
themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond  
appropriately.  
• This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to  
last as long as 10 years, the electronic components could fail at any time.  
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance.  
This alarm system should be tested weekly to make sure all sensors and transmitters are working properly.  
Installing an alarm system may make one eligible for lower insurance rates, but an alarm system is not a substitute for  
insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and  
continue to insure their lives and property.  
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved  
ones to learn about these developments.  
– 45 –  
 
–––––––––––––––––––––––––––– LIMITED WARRANTY–––––––––––––––––––––––––  
Terms and Conditions Applying to Sale of Equipment  
1. Limited Warranty.  
Any part of the system, including the wiring, installed under this Agreement which proves to be defective in material  
or workmanship within 90 days of the date of completion of installation will be repaired or replaced at ADT's option  
with a new functionally operative part. Labor and material required to repair or replace such defective components or  
to make mechanical adjustments to the system will be free of charge for a period of 90 days following the completion  
of the original installation.  
This warranty is extended only to the original consumer purchaser of the system and may be enforced only by such  
person.  
To obtain service under this warranty, call or write our local ADT Service Department at the telephone number or  
address found in your local yellow pages.  
Service pursuant to the warranty will be furnished only during ADT's normal working hours 8:00A.M. to 4:30P.M.,  
Monday through Friday, except holidays. Services rendered outside the normal working hours of ADT are not within  
the scope of this warranty and any services requested to be performed at such times shall be charged for at ADT's  
then applicable rates for labor and material.  
This warranty does not apply to the conditions listed below, and in the event customer calls ADT for service under the  
warranty and upon inspection it is found that one of these conditions has led to the inoperability or apparent  
inoperability of the system, a charge will be made for the service call of the ADT representative, whether or not he  
actually works on the system. Should it actually be necessary to make repairs to the system due to one of the  
"conditions Not Covered By Warranty", a charge will be made for such work at ADT's then applicable rates for labor  
and material.  
Conditions Not Covered By Warranty.  
A. Damage from accidents, acts of God, alterations, misuse, tampering or abuse. B. Failure of the customer to  
properly close or secure a door, window, or other point protected by a burglar alarm device. C. Failure of customer to  
properly follow operating instructions provided by ADT at time of installation or at a later date. D. Trouble in leased  
telephone. E. Trouble due to interruption of commercial power. F. Battery replacements.  
– 46 –  
 
This warranty is in lieu of all other express warranties. Any implied warranties of merchantability and fitness for a  
particular purpose are limited in duration to a period of 90 days from the date of completion of installation. The  
exclusive remedy of the customer hereunder shall be repair or replacement as stated above. Under no circumstances  
shall ADT be liable to the customer or any other person for incidental or consequential damages of any nature,  
including without limitation, damages for personal injury or damages to property, and, however occasioned, whether  
alleged as resulting from breach of warranty by ADT, the negligence of ADT, or otherwise, ADT's liability will in no  
event exceed the purchase price of the system. Some states may not allow limitations on how long an implied  
warranty lasts, or the exclusion or limitations of incidental or consequential damages, so the above limitations and  
exclusions may not apply to you, unless a longer period is required by applicable law. Any action against ADT in  
connection with a system must be commenced within one year after the cause of action has occurred.  
No agent, employee or representative of ADT nor any other person is authorized to modify this warranty in any  
respect.  
This warranty gives you specific legal rights and you may also have other rights which vary from state to state.  
2. Installation.  
ADT agrees to install the equipment in a workmanlike manner in accordance with the following conditions:  
A. Customer will make premises available without interruption during ADT normal working hours 8:00A.M. to  
4:30P.M., Monday through Friday, except Holidays. B. Customer understands that the installation will necessitate  
drilling into various parts of the premises: ADT intends, generally, to conceal wiring in the finished areas of the  
premises; however, there may be areas which, due to construction, decoration, or furnishing of the premises, ADT  
determines, in its sole discretion, that it would be impractical to conceal wiring and, in such cases, wiring will be  
exposed. C. Customer agrees to provide 110 VAC electrical outlets at designated locations for equipment requiring  
AC power. D. Customer to provide for lifting and replacing carpeting, if required, for installation of floor mats or wiring.  
––––––––––––––– ALL RIGHTS RESERVED –––––––––––––––––––––––––––––––––––––––––––––  
No part of this publication may be reproduced, stored in a retrieval system, or  
transmitted in any form, or by any means – electronic, mechanical, photocopying,  
recording, or otherwise without the written permission of ADT Security Systems,  
Inc. The material in this publication is for information purposes and subject to  
change without notice. ADT Security Systems, Inc. assumes no responsibility for  
any errors which may appear in this publication.  
– 47 –  
 
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •  
ADT Security Services, Inc. • One Town Center Rd. • Boca Raton, FL 33486  
Copyright © 2001  
¬1ꢁꢂꢃꢁꢄꢂ9ꢅ)lꢀ  
N7527-5V3  
Rev. B 1/01  
 

Aastra Telecom Telephone 5i Series User Manual
ACR Electronics Marine GPS System RLB 36 User Manual
Addonics Technologies Computer Accessories AEUDMACF User Manual
Aiwa VCR VX C131U User Manual
Allied Telesis Network Card AT 2916SX User Manual
ALS Industries CD Player DEH P5500MP User Manual
Amana Refrigerator W10180386A User Manual
AMX Stereo Amplifier AVB DA RGBHV 0103 User Manual
Axis Communications Home Security System Q7401 User Manual
Behringer Music Mixer BXR1800H User Manual