Carrier 30GX080 176 User Manual

30GX080-176  
30HX076-271  
Minimum Load Control Accessory  
50/60 Hz  
Installation Instructions  
Part Nos. 30HX-900---008, 30GX-900---004  
(60 Hz — 115-v Control)  
Part Nos. 30HX-900---009, 30GX-900---005  
(50 or 60 Hz — 230-v Control)  
Follow all safety codes. Wear safety glasses and work gloves.  
Use care in handling equipment.  
CONTENTS  
Page  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1  
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
Be sure power to equipment is shut off before perform-  
ing maintenance or service.  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6  
Step 1 — Examine Package Contents . . . . . . . . . 1  
Step 2 — Install Piping . . . . . . . . . . . . . . . . . . . . . . . 2  
• REMOVE MINIMUM LOAD PORT PLUGS AND  
INSTALL FITTINGS  
• INSTALL PIPING  
• INSTALL BALL AND SOLENOID VALVES  
• CONNECT PIPING  
IMPORTANT: When removing refrigerant, use an  
approved refrigerant recovery device. Do not vent re-  
frigerant into the atmosphere.  
Step 3 — Dehydrate and Recharge Circuit . . . . . 3  
Step 4 — Install Control Wiring . . . . . . . . . . . . . . . 4  
• 30HX UNITS  
INTRODUCTION  
The minimum load control accessory allows 30HX and  
30GX chillers to have their capacities decreased below the  
standard fully unloaded condition. The accessory provides  
more precise control of leaving fluid temperature during light  
load conditions.  
The 30GX and 30HX chillers have a dual-circuit design.  
Each minimum load control accessory package contains the  
items required for both circuits. Because of an automatic lead/  
lag feature on the chillers, the accessory should be installed  
on both circuits.  
• 30GX UNITS  
• ALL UNITS  
Step 5 — Configure Unit for Minimum  
Load Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Step 6 — Test Minimum Load Relay  
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Step 7 — Adjust Setting of Minimum Load  
Ball Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
SAFETY CONSIDERATIONS  
INSTALLATION  
Installing, starting up, and servicing air-conditioning equip-  
ment can be hazardous due to system pressures, electrical  
components, and equipment location.  
Only trained, qualified installers and service technicians  
should install, start up, and service this equipment.  
When working on air-conditioning equipment, observe pre-  
cautions in the literature and on tags, stickers, and labels at-  
tached to the equipment.  
Step 1 — Examine Package Contents — Pack-  
age includes solenoid valves, ball valves, Swagelokcon-  
nectors, and instructions. The kit for 30GX units also con-  
tains a junction box, junction box cover, and conduit. Examine  
each item. If any part is damaged or missing, file a claim  
immediately with the shipper. See Table 1 for accessory pack-  
age contents and field-supplied material.  
Table 1 — Accessory Package Contents and Field-Supplied Material  
ACCESSORY PART NUMBER  
ACCESSORY PACKAGE  
COMPONENTS  
30HX-900---008  
30HX-900---009  
30GX-900---004  
(2) EF23JX212  
(2) EP71BA201  
(2) DC09CA307  
HX30FZ001  
30GX-900---005  
(2) EF23JX231  
(2) EP71BA201  
(2) DC09CA307  
HX30FZ001  
Solenoid Valve  
Ball Valve  
(2) EF23JX212  
(2) EF23JX231  
(2) EP71BA201  
(2) EP71BA201  
Swagelok Connector  
Junction Box  
(4) DC09CA307  
(4) DC09CA307  
Junction Box Cover  
Watertight Conduit  
HX38ZZ001  
HX38ZZ001  
99CD2121AC028  
99CD2121AC028  
FIELD SUPPLIED MATERIAL — REQUIRED PARTS (Ordered Separately)  
8-in. OD Copper Tubing, Wiring, Conduit,  
Thread Sealant, Electrical Supplies  
5
Field Supplied  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 2  
PC 903  
Catalog No. 563-056  
Printed in U.S.A.  
Form 30GX,HX-2SI  
Pg 1  
1-97  
Replaces: New  
Tab 5c  
INSTALL BALLAND SOLENOID VALVES — Using good  
IMPORTANT: Do NOT overtighten the fittings. Over-  
tightening the fittings can deform the tube ends and  
cause leaks.  
piping practice, braze ball valve and solenoid valve into  
5
8-in. minimum load piping. Fig. 2 shows a typical 30HX  
installation and Fig. 3 shows a typical 30GX installation, in-  
cluding valve locations and orientation. Ensure that ball valve  
is fully open, and that both the ball and solenoid valve are  
protected from excess heat during brazing process. Wrap wet  
cloths around valve bodies during brazing to prevent dam-  
age to the valves from heat.  
30GX UNITS ONLY — Using good brazing practice, braze  
the 58-in. minimum load tubing to the copper nipple on the  
discharge line (minimum load port) between the condenser  
coil and oil separator. See Fig. 1 and 3.  
IMPORTANT: When installing solenoid valve, make  
sure that flow direction arrow on valve body points  
towards the cooler. The minimum load control will not  
function correctly if this valve is installed backwards.  
Step 3 — Dehydrate and Recharge Circuit  
When piping has been completed, leak test the assem-  
bly. If one of the Swagelok fittings leaks, slowly tighten the  
compression nut until the leak stops. If this does not fix the  
leak, the connection must be reinstalled using a new ferrule  
and backup ring in the fitting. Contact your Carrier repre-  
sentative for assistance in locating these parts.  
After leak testing, evacuate, dehydrate, and recharge the  
circuit using an approved refrigerant recovery device. Cor-  
rect type and amount of refrigerant are listed on unit name-  
plate and in base unit documentation.  
CONNECT PIPING — Check the ends of the tubes where  
they will be inserted into the Swagelokfittings. To avoid  
leaks, tube ends must be round and free of burrs, nicks, and  
grooves.  
Insert tube ends into fittings as far as they will go. When  
tube bottoms out, tighten the compression nut finger-tight  
while holding the fitting body. Use backup wrench to hold  
fitting body and tighten compression nut another 114 turns.  
Fig. 2 — Installing Fittings and Valves, 30HX (Typical)  
3
Fig. 3 — Installing Valves, 30GX  
30GX UNITS — Install the accessory junction box included  
Step 4 — Install Control Wiring  
with this kit in the position shown on the 30GX chiller in  
Fig. 3. Route the waterproof conduit included with this kit  
between the accessory junction box and the factory-installed  
junction box. See Fig. 3 and 4. Route field-supplied conduits  
from the solenoid valves to the accessory junction box.  
Be sure all power to the unit is off before proceeding.  
Lock out and safety-tag all disconnects.  
ALL UNITS — Using good wiring practice, connect a white  
wire from the solenoid valve on circuit A to a white wire  
from the solenoid valve on circuit B. Connect both wires to  
the white wire in the factory-installed junction box (30GX),  
or unit wiring harness labelled ‘‘MLC-A& B(30HXA, HXC).  
Connect a pink wire from the solenoid valve on circuit A  
to the pink wire in the factory-installed junction box (30GX),  
or unit wiring harness labelled MLC-A (30HXA, HXC).  
Connect a gray wire from the solenoid valve on circuit B  
to the gray wire in the factory-installed junction box (30GX),  
or unit wiring harness labelled MLC-B (30HXA, HXC).  
Figure 4 shows the correct wiring for the minimum load  
control and the location of the wiring connection points on  
the chiller.  
Wires between field-installed components and unit control  
box must be enclosed in field-supplied conduit. Follow all  
local codes and NEC (National Electrical Code, U.S.A.). Wire  
size must be no. 16 AWG (American Wire Gage) (1.5 mm2)  
minimum. See Fig. 4 for field wiring.  
30HX UNITS — Remove the screws holding the right-side  
access panel to the unit control box. Remove the right-side  
access panel and store in a safe area.  
Route wires through field-supplied conduit and attach the  
conduit to the unit control box, using a suitable conduit fit-  
7
ting and one of the available 8-in. knockout openings. At-  
tach the other end of the conduit to the solenoid valve, using  
a suitable fitting. Repeat for the other circuit.  
4
30GX080-176  
30HX076-271  
LEGEND  
MLC  
TB  
Minimum Load Control  
Terminal Block  
NOTE: See Fig. 3 for locations of junction  
boxes on unit.  
Fig. 4 — Minimum Load Control Wiring  
5
Step 5 — Configure Unit for Minimum Load Con-  
8. Press  
for Circuit A.  
to turn off the minimum load valve relay  
trol — Once the piping installation and wiring installation  
are complete, the chiller must be configured for minimum  
load control operation. This may be done using the unit key-  
pad (HSIO-2). Set the LOCAL/OFF switch in the OFF  
position.  
To check the operation of the solenoid valve on Circuit B,  
follow the same procedure as the preceding, but enter  
enter  
in Step 1, instead of  
. The display  
screens will be for Circuit B instead of A.  
1. Press  
on the keypad.  
2. Press the down arrow  
until the display reads:  
After testing is complete, recheck all electrical connec-  
tions for proper location and tightness. For 30HX units, re-  
place and secure the access panels for the unit control box.  
For 30GX units, secure the junction box covers to the junc-  
tion boxes.  
MIN. LOAD VALVE SELECT  
DISABLE  
3. To enable the minimum load valve feature, press  
.
Step 7 — Adjust Setting of Minimum Load Ball  
4. The display may read as follows. (If not, skip to Step 7.)  
Valve — Before the installation is complete, the mini-  
mum load ball valve must be adjusted to suit the application.  
Calibrate one circuit at a time as follows:  
PASSWORD PROTECTED FUNCTION  
ENTER PASSWORD  
5. Press  
.
1. Adjust the ball valve so that it is approximately half open.  
6. The HSIO-2 again displays the following:  
2. Operate the chiller in Manual Control mode, with one cir-  
cuit operating, and all compressor loaders deenergized.  
NOTE: Operation of the chiller in Manual Control mode is  
described in the Controls, Start-Up, Operation, and Trouble-  
shooting Guide that is included with the 30GX,HX  
Ecologic™ chillers.  
3. Record the cooler T (the difference between cooler en-  
tering fluid temperature and cooler leaving fluid tempera-  
ture) at this fully unloaded condition.  
MIN. LOAD VALVE SELECT  
DISABLE  
7. Press  
. The display changes to:  
MIN. LOAD VALVE SELECT  
ENABLE  
The chiller is now configured for minimum load valve  
control.  
4. Use the Manual Control feature to enable the minimum  
load valve for the circuit that is operating.  
Step 6 — Test Minimum Load Relay Outputs  
After the accessory components are installed and the unit  
is recharged and reconfigured, test the operation of the relay  
and solenoid valve using the Quick Test software function.  
Test Circuit A as follows (the LOCAL/OFF switch must be  
in the OFF position):  
5. Observe and record the cooler T with the minimum load  
valve energized.  
6. Adjust the minimum load ball valve until the cooler tem-  
perature difference reading from Step 5 is equal to half of  
the temperature difference reading from Step 3.  
1. Press  
on the HSIO-2 keypad.  
7. Open the ball valve to decrease the temperature differ-  
ence or close the ball valve to increase the temperature  
difference (T). When the valve is adjusted correctly,  
the difference between cooler entering and leaving fluid  
temperatures when the minimum load control is ener-  
gized must be at least half of the temperature difference  
when the minimum load control is deenergized. For ex-  
ample, if the difference between the cooler entering and  
leaving water temperature is 3° F with the valve deen-  
ergized, then the difference between cooler entering and  
leaving water temperature must be at least 1.5° F with the  
valve energized.  
2. Press the down arrow  
until the display reads:  
MIN. LOAD VALVE A  
RELAY IS OFF  
3. Press  
.
4. The display may read as follows. (If not, skip to Step 7.)  
PASSWORD PROTECTED FUNCTION  
ENTER PASSWORD  
5. Press  
.
6. The HSIO-2 again displays the following:  
Once the outputs have been tested and the ball valve ad-  
justed, the installation is complete.  
MIN. LOAD VALVE A  
RELAY IS OFF  
7. Press  
to energize the relay. The display reads:  
MIN. LOAD VALVE A  
RELAY IS ON  
An audible click will be heard. Verify that the solenoid  
valve for Circuit A is energized.  
6
Copyright 1997 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 2  
PC 903  
Catalog No. 563-056  
Printed in U.S.A.  
Form 30GX,HX-2SI  
Pg 8  
1-97  
Replaces: New  
Tab 5c  

Aluratek AUCS02F User Manual
Boston Acoustics SPEAKER SYSTEM PRI685 User Manual
Brother MFC 8870DW User Manual
Carrier 38AU User Manual
Enerco HSU 75 User Manual
Friedrich MR12C1H User Manual
Friedrich PE09R__B User Manual
Goodman Mfg CKLB24 1G User Manual
Heat Controller Inc Air Conditioner 125 TON User Manual
Honda Automobiles 2 DOOR DX User Manual